4-21
Note 2. The factory setting for the 3G3EV-A4015-CUE is “3.”
Note 3. With the 400-VAC class, the continuous output current cannot be used to 100%
of the rated value if the constant is set to “5” for Inverters of 0.75 kW or less or if it
is set to “4” or “5” for an Inverter of 1.5 kW.
Set the constant so that the continuous output current does not exceed the val-
ues shown in the following tables.
400-VAC Inverters of 0.75 kW or Less
Carrier frequency set value
Max. continuous output current
1 to 4
Up to 100% of the rated output
5
Up to 90% of the rated output
400-VAC Inverter of 1.5 kW
Carrier frequency set value
Max. continuous output current
1 to 3
Up to 100% of the rated output
4
Up to 85% of the rated output
5
Up to 75% of the rated output
Preparing for Operation