• Power cables and signal cables adversely affect each other. Do not wire them in parallel.
• Noise induction may occur if the Box PC is installed in a panel that includes high-voltage devi-
ces. Wire and install them as far apart as possible.
• Either install the Box PC a minimum of 200 mm away from high-voltage lines or power lines, or
place the high-voltage lines or power lines in metal tubing and completely ground the metal tub-
ing to 100 Ω or less.
Example: Separating an OMRON product from Power Lines
Metal tubing
200 mm
200 mm
High-voltage power panel
Power lines
Power lines
Ground of
100 Ω or less
OMRON
product
OMRON
product
Wiring Ducts
Whenever possible, route the cables and wires through wiring ducts.
Install the wiring ducts so that it is easy to route the wires from the Industrial Box PC directly into
the duct.
Additional Information
Refer to
on page 5 - 16 for the minimum required distances.
It is convenient to use wiring ducts that have the same depth as the Industrial Box PC.
Duct
Product
Other Precautions
Basic I/O Units have both plus and minus commons, so pay attention to the polarity when wiring.
5 Installation
5 - 24
NY-series Industrial Box PC User's Manual (W553)
Summary of Contents for NYB17-11
Page 30: ...Sections in this Manual 28 NY series Industrial Box PC User s Manual W553...
Page 38: ...1 Overview 1 8 NY series Industrial Box PC User s Manual W553...
Page 60: ...2 Hardware 2 22 NY series Industrial Box PC User s Manual W553...
Page 218: ...7 Maintenance 7 42 NY series Industrial Box PC User s Manual W553...
Page 239: ...I Index I 1 NY series Industrial Box PC User s Manual W553 I...
Page 242: ......
Page 243: ......