4-3-3
Temperature
The temperature inside a control panel may be at least 10 to 15°C higher than outside the panel. Im-
plement the following measures against overheating at the installation site and in the control panel,
and allow a sufficient margin for the temperature.
Distance for Cooling
Adequate airflow around the Industrial Panel PC is required.
Additional Information
• The ambient temperature must be within the operating range.
3-4-1 Operation Environment Specifications
on page 3-11 for temperature specifica-
tions.
• Allow space to accommodate for the bending radius of the cables.
on page 2-8 for cable bending requirements and connector
clearances.
Provide enough space for good air flow and ensure the following minimum distances are observed
around the sides of the Industrial Panel PC.
Z
X
X
Y
Y
A
A
Landscape orientation.
Item
Minimum distance
X
50 mm
Y
100 mm
Z
50 mm
4 Installation
4-9
NY-series NYE Industrial Panel PC Conversion Guideline for NS-series products (P157)
4-3 Mount
4
4-3-3
T
emperature