Modbus Connections
Section 12-5
12-5 Modbus Connections
12-5-1 NV3W
12-5-2 NV4W/NV3Q
12-5-3 Modbus Connections to OMRON EJ1 Temperature Controller
NV3W error codes are displayed as "ER" followed by the two-digit
code.NV4W and NV3Q error codes are displayed as "ER00" followed by the
two digit error code.
The notation for the NV3W is used in the following table. When using the
NV4W or NV3Q, "00" will be displayed after "ER."
Error code
Description
Cause and countermeasure
ERFF
Timeout Error
The PLC did not return a
response.
1. The cable connecting the PLC is disconnected. Check the cable for
incorrect wiring or disconnections.
2. A temporary error was caused by noise or other factor. Cycle the pow-
er to the PLC or PT.
ERFE
Response Error
An error response was
returned by the external
device.
Check the data that was returned by the external device.
Error code
Description
Cause and countermeasure
ER0001
Timeout Error
The PLC did not return a
response.
1. The cable connecting the PLC is disconnected. Check the cable for
incorrect wiring or disconnections.
2. A temporary error was caused by noise or other factor. Cycle the pow-
er to the PLC or PT.
ERFFFE
Response Error
An error response was
returned by the external
device.
Check the data that was returned by the external device.
Error code
Description
Cause and countermeasure
ER01
Function code error
The function code is not supported.
ER02
Variable address error
1. There is an error in the write start address.
2. There is an error in the read start address.
ER03
Variable data error
1. The command is too short.
2. The command is too long.
3. The number of elements exceeds the maximum value.
4. The number of elements and data do not match.
5. The number of elements times two does not match the byte count.
6. The write data is outside the setting range.
7. An attempt was made to write to a read-only variable.
ER04
Operation error
1. The operation command could not be received and was not executed.
2. The operation was not executed because data was being backed up.
3. The operation was not executed because a reset was being pro-
cessed (including when starting).
4. The operation was not executed because the Controller was in Tuning
Mode.
Summary of Contents for NV3Q Series
Page 1: ...Cat No V105 E1 02 Programmable Terminals NV Series NV3W NV4W NV3Q HOST CONNECTION MANUAL ...
Page 2: ......
Page 3: ...NV Series NV3W NV4W NV3Q Programmable Terminals Produced December 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 16: ...xvi ...
Page 20: ...xx ...
Page 68: ...44 S7 200 Series Section 5 1 ...
Page 69: ...45 SECTION 6 Connecting to LG PLCs 6 1 MASKER K Cnet Series 46 6 1 1 Connection Method 46 ...
Page 72: ...48 MASKER K Cnet Series Section 6 1 ...
Page 76: ...52 FA M3 Series Section 7 1 ...
Page 110: ...86 Web Controller Series Section 9 3 ...
Page 120: ...96 Modbus RTU Mode Temperature Controller Section 10 3 ...
Page 142: ...118 Modbus Connections Section 12 5 ...
Page 144: ...120 Revision History ...