113
Mitsubishi Electric FX-series PLC Connections
Section 12-2
12-2 Mitsubishi Electric FX-series PLC Connections
12-2-1 NV3W
12-2-2 NV4W/NV3Q
Error code
Description
Cause and countermeasure
ERFF
Timeout Error
The PLC did not return a
response.
1. The cable connecting the PLC is disconnected. Check the cable for
incorrect wiring or disconnections.
2. A temporary error was caused by noise or other factor. Cycle the pow-
er to the PLC or PT.
ER10
Data Error
An error occurred in the data
during communications.
Make sure that the communications settings are correct.
ER12
Overrun Error
The PT cannot receive data.
The PLC may be running out of control.
ER61
PLC Error
The PLC returned a NAK
error.
Check the PLC settings.
Error code
Description
Cause and countermeasure
ERFFFE
PLC Error
The PLC returned a NAK
error.
Check the PLC settings.
Summary of Contents for NV3Q Series
Page 1: ...Cat No V105 E1 02 Programmable Terminals NV Series NV3W NV4W NV3Q HOST CONNECTION MANUAL ...
Page 2: ......
Page 3: ...NV Series NV3W NV4W NV3Q Programmable Terminals Produced December 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 16: ...xvi ...
Page 20: ...xx ...
Page 68: ...44 S7 200 Series Section 5 1 ...
Page 69: ...45 SECTION 6 Connecting to LG PLCs 6 1 MASKER K Cnet Series 46 6 1 1 Connection Method 46 ...
Page 72: ...48 MASKER K Cnet Series Section 6 1 ...
Page 76: ...52 FA M3 Series Section 7 1 ...
Page 110: ...86 Web Controller Series Section 9 3 ...
Page 120: ...96 Modbus RTU Mode Temperature Controller Section 10 3 ...
Page 142: ...118 Modbus Connections Section 12 5 ...
Page 144: ...120 Revision History ...