114
Panasonic Electric Works FP-series PLC Connections
Section 12-3
12-3 Panasonic Electric Works FP-series PLC Connections
12-3-1 NV3W
12-3-2 NV4W/NV3Q
Error code
Description
Cause and countermeasure
ER21
Data Error
An error occurred in the data
during communications.
1. There is a mistake in the communications settings. Make sure that the
baud rates and transmission formats are correct for the PLC and PT.
2. A temporary error was caused by noise or other factor. Cycle the pow-
er to the PLC and PT.
ER22
Overrun Error
The PT cannot receive data.
The reception buffer in the CPU Unit overflowed. An error may have
occurred in the PLC. Cycle the power to the PLC and PT.
ER40
BCC Error
An error occurred in the data
during communications.
1. A temporary error was caused by noise or other factor. Cycle the pow-
er to the PLC and PT.
2. An error may have occurred in the CPU Unit. Cycle the power to the
PLC and PT.
ER41
Format Error
A command that is not valid
for the protocol was sent to
the PLC.
1. A temporary error was caused by noise or other factor. Cycle the pow-
er to the PLC and PT.
2. An error may have occurred in the CPU Unit. Cycle the power to the
PLC and PT.
ER42
Not Supported Error
A command that is not sup-
ported by the PT was sent to
the PLC.
1. A temporary error was caused by noise or other factor. Cycle the pow-
er to the PLC and PT.
2. An error may have occurred in the CPU Unit. Cycle the power to the
PLC and PT.
ER53
Busy Error
The PLC is processing
another command.
The PLC is transferring a large quantity of data on another RS-232C
port. Wait until the error clears.
ER60
Parameter Error
The value set for the parameter does not exist or cannot be used.
ER61
Data Error
There was a mistake in a reg-
ister or relay address.
A register or relay that does not exist in the PLC was specified when
creating screens on the NV-Designer. Correct the addresses used by
parts, to output the clock data, etc.
Error code
Description
Cause and countermeasure
ER0021
Data Error
An error occurred in the data
during communications.
1. There is a mistake in the communications settings. Make sure that the
baud rates and transmission formats are correct for the PLC and PT.
2. A temporary error was caused by noise or other factor. Cycle the pow-
er to the PLC and PT.
ER0022
Overrun Error
The PT cannot receive data.
The reception buffer in the CPU Unit overflowed. An error may have
occurred in the PLC. Cycle the power to the PLC and PT.
ER0040
BCC Error
An error occurred in the data
during communications.
1. A temporary error was caused by noise or other factor. Cycle the pow-
er to the PLC and PT.
2. An error may have occurred in the CPU Unit. Cycle the power to the
PLC and PT.
ER0041
Format Error
A command that is not valid
for the protocol was sent to
the PLC.
1. A temporary error was caused by noise or other factor. Cycle the pow-
er to the PLC and PT.
2. An error may have occurred in the CPU Unit. Cycle the power to the
PLC and PT.
ER0042
Not Supported Error
A command that is not sup-
ported by the PT was sent to
the PLC.
1. A temporary error was caused by noise or other factor. Cycle the pow-
er to the PLC and PT.
2. An error may have occurred in the CPU Unit. Cycle the power to the
PLC and PT.
ER0053
Busy Error
The PLC is processing
another command.
The PLC is transferring a large quantity of data on another RS-232C
port. Wait until the error clears.
Summary of Contents for NV3Q Series
Page 1: ...Cat No V105 E1 02 Programmable Terminals NV Series NV3W NV4W NV3Q HOST CONNECTION MANUAL ...
Page 2: ......
Page 3: ...NV Series NV3W NV4W NV3Q Programmable Terminals Produced December 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 16: ...xvi ...
Page 20: ...xx ...
Page 68: ...44 S7 200 Series Section 5 1 ...
Page 69: ...45 SECTION 6 Connecting to LG PLCs 6 1 MASKER K Cnet Series 46 6 1 1 Connection Method 46 ...
Page 72: ...48 MASKER K Cnet Series Section 6 1 ...
Page 76: ...52 FA M3 Series Section 7 1 ...
Page 110: ...86 Web Controller Series Section 9 3 ...
Page 120: ...96 Modbus RTU Mode Temperature Controller Section 10 3 ...
Page 142: ...118 Modbus Connections Section 12 5 ...
Page 144: ...120 Revision History ...