91
Modbus (RTU Mode)
Section 10-2
■
PLC Communications Settings
Item
Setting
Slave address
1
Mode
RTU mode
Baud rate
19,200 bps
Data length
8
Stop bits
1
Parity
Even
Additional Information
The following function codes can be used for Modbus-RTU communications from
the master. Select the function codes for the areas of the addresses that are set.
Function code (hex): Meaning
01: Read coil state
02: Read input bit state
03: Read holding register contents
04: Read input register contents
05: Write coil state for bits
0F: Write coil states for words
10: Write register contents for multiple words
Refer to the Modbus communications specifications and the manuals for the
slave devices for details on function codes.