CLT- & CLX-PWS75

 

Terminal Block & Module Locations (Single-wide Enclosure) 

Functional Summary 

GROUNDING

TERMINAL

BLOCK

MODULE

TERMINAL

BLOCK

 

The Crestron 75 Watt Power Supply Terminal Block and 
Module (CLT-PWS75 and CLX-PWS75, respectively) 
are considered a single entity and must be used together. 
They ship separately to permit termination of the field 
wiring to the CLT-PWS75 prior to installation of the 
CLX-PWS75, as described in this guide. The  
CLX-PWS75 is a power supply module that provides up 
to 75 Watts of Cresnet power to Crestron equipment. The 
terminal block and module can be mounted in any 
Crestron Automation Enclosure (CAEN-Series 
Enclosures, see warning below). The terminal block is 
designed to terminate the circuit feed (HOT and 
NEUTRAL) and distribute the power to a connector on a 
supplied cable assembly (LOAD) that connects to the 
power supply module. The power supply module operates 
with an input of 100 to 250 VAC, 2.3A (maximum). The 
power supply module has a fuse that protects the 24 VDC 
output. If the network power lines are shorted, the fuse is 
blown. As a result, the NET POWER LED extinguishes.  

Industry Compliance 

This unit has been manufactured to comply with UL’s 
Standards for Safety in Canada and the United States. 
Formal approval is pending.  

Terminal Block & Module Locations (Double-wide Enclosure) 

Installation 

MODULE

TERMINAL BLOCK

(RIGHT)

GROUNDING TERMINAL BLOCKS

TERMINAL BLOCK

(LEFT)

MODULE

 

The terminal block and module must be mounted into a 
Crestron Automation Enclosure by a licensed electrician, 
in accordance with all national and local codes.  

CAUTION:  

This equipment is for indoor use only and 

needs to be air-cooled. Mount in a well-ventilated area. 
The ambient temperature must be 32

°

F to 104

°

F (0

°

C to 

40

°

C). The relative humidity must be 0% to 90% (non-

condensing).  

CAUTION:

 Terminal blocks and modules must be 

installed in the lowest slot of an enclosure. The only 
devices in an enclosure that may be placed beneath the 
block and module is the Crestron PAC2 Automation 
Control System or CAEN-BLOCK Termination Block. 
Refer to the illustrations shown for recommended 
installation locations.  

Crestron Electronics, Inc.

 

Installation Guide – DOC. 6348

 

15 Volvo Drive   Rockleigh, NJ 07647

 

(2012603)

   

Tel: 888.CRESTRON

 

06.05   

 

Fax: 201.767.7576

  

Specifications subject to 

 

www.crestron.com

 

change without notice.

 

Summary of Contents for CLT-PWS75

Page 1: ...se is blown As a result the NET POWER LED extinguishes Industry Compliance This unit has been manufactured to comply with UL s Standards for Safety in Canada and the United States Formal approval is pending Terminal Block Module Locations Double wide Enclosure Installation MODULE TERMINAL BLOCK RIGHT GROUNDING TERMINAL BLOCKS TERMINAL BLOCK LEFT MODULE The terminal block and module must be mounted...

Page 2: ... to the terminal block per the markings provided on the wiring label as shown in the following diagram Terminal blocks accept one 14 10 AWG wire Wires should be stripped to inch Tighten terminal blocks to 9 in lbs NOTE HOT and NEUTRAL lines can be jumped to other terminal blocks in the enclosure 3 Grounding terminal blocks are available in the cabinet for termination of ground wires Tighten to 35 ...

Page 3: ...e connected must be taken into consideration If Cresnet units are to be daisy chained on the run the Cresnet power usage of each network device to be daisy chained must be added together to determine the Cresnet power usage of the entire chain If the unit is a home run from a Crestron system power supply network port the Cresnet power usage of that unit is the Cresnet power usage of the entire run...

Page 4: ...em NOTE Never connect multiple modules in parallel Hookup Procedure 1 Connect each network device to the appropriate network connector on the module 2 Connect AC power to the module 3 If a PC running SIMPL Windows is available connect the PC to the Cresnet system via the computer port on the control system 4 Establish communications with the control system as described in the latest version of the...

Page 5: ...DEVICE NETWORK DATA LINK TO ADDITIONAL EXPANSION CLX PWS75 CLX PWS75 DAISY CHAIN METHOD NETWORK DEVICE NETWORK DEVICE CLX PWS75 POWER EXPANSION NETWORK DATA LINK TO EXPANSION CLX PWS75 HOME RUN METHOD CONTROL SYSTEM Installation Guide DOC 6348 Terminal Block Module CLT CLX PWS75 5 ...

Page 6: ...n freight costs shall be paid by the purchaser CRESTRON Limited Warranty CRESTRON ELECTRONICS Inc warrants its products to be free from manufacturing defects in materials and workmanship under normal use for a period of three 3 years from the date of purchase from CRESTRON with the following exceptions disk drives and any other moving or rotating mechanical parts pan tilt heads and power supplies ...

Reviews: