Modbus Slave (RTU Mode)
Section 11-1
Function Code 06: Write data register, one word
■
Commands
■
Responses
The response will contain the same message as the command.
PT slave
address
Function
code
06 hex
Data register
address,
upper byte
Data register
address,
lower byte
Write data,
upper byte
Write data,
lower byte
Error check,
upper byte
Error check,
lower byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
PT slave
address
Function
code
06 hex
Data register
address,
upper byte
Data register
address,
lower byte
Write data,
upper byte
Write data,
lower byte
Error check,
upper byte
Error check,
lower byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
Item
Function
PT slave address Specify the slave address of the PT to which to send the message.
For slave address 20, specify 14 hex.
Function code
Specify 06 hex.
Data register
address
Specify the data register address to write in hexadecimal.
For GDT510, specify 01 hex, FE hex.
Write data
Send the value to write with the upper byte first, followed by the
lower byte. To write 1234 hex, specify 12 hex, 34 hex.
Error check
The CRC-16 values are sent and received.
Summary of Contents for NV3Q Series
Page 1: ...Cat No V105 E1 02 Programmable Terminals NV Series NV3W NV4W NV3Q HOST CONNECTION MANUAL ...
Page 2: ......
Page 3: ...NV Series NV3W NV4W NV3Q Programmable Terminals Produced December 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 16: ...xvi ...
Page 20: ...xx ...
Page 68: ...44 S7 200 Series Section 5 1 ...
Page 69: ...45 SECTION 6 Connecting to LG PLCs 6 1 MASKER K Cnet Series 46 6 1 1 Connection Method 46 ...
Page 72: ...48 MASKER K Cnet Series Section 6 1 ...
Page 76: ...52 FA M3 Series Section 7 1 ...
Page 110: ...86 Web Controller Series Section 9 3 ...
Page 120: ...96 Modbus RTU Mode Temperature Controller Section 10 3 ...
Page 142: ...118 Modbus Connections Section 12 5 ...
Page 144: ...120 Revision History ...