KP100G
23
(2) Unscrew the cable gland and prepare AC and Ground(GND) cable. Remove the rubber bushing from inside the AC connector socket.
Fig, 5-19 Remove the rubber plug
(3) Insert the provided rubber bushing into the AC connector socket.
Two types of rubber bushing for AC connection as illustrated in Fig, 5-3.
z
The rubber bushing with 4 holes is used for connection with 4 individual cables.
z
The rubber bushing with 1 hole is used for connection with multiple-cable.
Rubber sealing for GND cable is already inserted inside of connector.
Now insert the four wires of the AC cable and one wire of GND cable into the bushing holes.
Please note that cross-sectional area of 4 mm
2
is allowed size for AC wires; L1, L2, L3, N, and that a cross-sectional area of 10 mm
2
or AWG8 is
allowed for GND.
Fig, 5-20 Insert the
rubber bushing with holes
(4) Fix 4 wire to L1 (R), L2 (S), L3 (T), and N (Neutral), and a wire to G (Ground).
Fig, 5-21 Connect the AC wire
Rubber bushing (no hole)
2 types rubber bushings for
AC connector
Rubber sealing for GND
connector