Output Test
This function is convenient for checking a system to which the K3NX is con-
nected, especially when some inputs cannot be operated. The K3NX simulates
an input signal to check the output conditions.
Note The K3NX has output according to the simulated input in this mode. If there is
any device connected to the output of the K3NX, be sure that the output will not
have a negative influence on the device before testing the system.
•
Follow the steps described below to perform the test.
1, 2, 3...
1. While the K3NX is in RUN mode, press the Mode Key for more than one se-
cond to set the K3NX to the setting mode.
2. Repeatedly press the Mode Key until
test
output test setting is displayed.
RUN mode
Setting Mode
1 second
Setting values menu
Scaling menu
Output test
Option menu
Setup menu
sUset
test
opt
setup
scale
3. Press the Mode Key for more than one second to display 0, which is a simu-
lated input value.
4. The simulated input value increases when the Up Key is pressed. Compara-
tive outputs are output according to the output pattern that has been preset.
5. The simulated input value decreases when the Shift Key is pressed. Com-
parative outputs are output according to the output pattern that has been
preset.
6. Press the Escape Key after testing. The
test
output test setting will be dis-
played again.
7. Press the Escape Key to return to the RUN mode.
•
To change the simulated input value continuously, keep pressing the Up or
Shift Key.
Output Test
Section 5-2