4-1
Forced-zero
•
The forced-zero function enables the K3NX to shift the process value to 0,
which allows relative object measurement with ease when one of the following
is activated in RUN mode.
The RESET/TEACH Key is pressed while the process value is displayed.
The external ZERO input signal is turned ON.
The K3NX receives the forced-zero command through communications.
•
The ZERO indicator is lit while the K3NX is in forced-zero state.
•
The K3NX retains the forced-zero value even when the power is switched off.
•
The process value can be prohibited against change when the forced-zero
prohibit setting is ON in protect mode.
Display value
Process value
Process value after
executing the forced-
zero
Forced-zero
input
Forced-zero value
(shifted value)
•
The following is the relationship between the process value after scaling and
display value after the process value is shifted to zero.
Display value after executing the forced-zero =
Process value after scaling – Shifted value
Therefore, if the process value after scaling is shifted to zero, the scaled pro-
cess value and the display value after executing the forced-zero will not coin-
cide with each other.
Display value
Scaled process value
Forced-zero value
Process value after
executing the forced-
zero
(shifted value)
•
Forced-zero state will be canceled if one of the following is performed.
The RESET/TEACH Key is pressed for longer than one second while the
process value is displayed.
The K3NX receives the forced-zero cancel command through communica-
tions.
Two-coordinate input scale (input 1 and input 2) is changed in setting mode.
Forced-zero
Section 4