3.7 Control Circuit Wiring
NOTICE: Do not solder the ends of wire connections to the drive. Soldered wire connections can loosen over time. Improper wiring
practices could result in drive malfunction due to loose terminal connections.
S1
S2
S3
S4
S5
24 V
I
V
+24
V 8
mA
SC
AM
AC
+
-
AM
+V
A1
AC
2 k
MA
MB
MC
Forward run/stop
Reverse run/stop
External fault
Fault reset
Digital inputs
(default setting)
J1000
Control circuit
Multi-step
speed 1
main/aux switch
DIP switch S1
Option unit
connector
<1>
DIP
switch S3
Shield ground
terminal
0 to +10 V (20 k )
(0)4 to 20 mA (250 )
Setting power supply
+10.5 max. 20 mA
Digital output
250 Vac, 10 mA to 1 A
30 Vdc, 10 mA to 1 A
(default setting)
Main speed
frequency
reference.
Multi-function
programmable
Sink
Source
<2>
<3>
0 to +10 Vdc
(2 mA)
Analog monitor
output
Monitor
output
main circuit terminal
shielded line
twisted-pair shielded line
control terminal
Figure 3.10 Control Circuit Connection Diagram
<1> Connected using sequence input signal (S1 to S5) from NPN transistor; Default: sink mode (0 V com)
<2> Use only the +24 V internal power supply in sinking mode; the source mode requires an external power supply.
Refer
to I/O Connections on page 44
.
<3> Minimum load: 5 Vdc, 10 mA (reference value).
u
Control Circuit Terminal Block Functions
Drive parameters determine which functions apply to the multi-function digital inputs (S1 to S5), multi-function digital
outputs (MA, MB, MC), and multi-function analog output (AM). The default is called out next to each terminal in
Figure
3.10
.
WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a drive
with untested control circuits could result in death or serious injury.
WARNING! Confirm the drive I/O signals and external sequence before starting test run. Failure to comply may result in death or serious
injury.
n
Input Terminals
Table 3.6 Control Circuit Input Terminals
Type
No.
Terminal Name (Function)
Function (Signal Level) Default Setting
Multi-Function
Digital Inputs
S1
Multi-function input 1 (Closed: Forward run, Open:
Stop)
24 Vdc, 8 mA
Note:
Drive preset to sinking mode. When using source mode, set
DIP switch S3 to allow for a 24 Vdc (±10%) external power supply.
Refer to Sinking/Sourcing Mode Switch on page 44
.
S2
Multi-function input 2 (Closed: Reverse run, Open:
Stop)
S3
Multi-function input 3 (External fault (N.O.)
S4
Multi-function input 4 (Fault reset)
S5
Multi-function input 5 (Multi-step speed reference 1)
SC
Multi-function input common (Control common)
Sequence common
3.7 Control Circuit Wiring
40