Item
Specification
Cooling Method
JZAB0P1 to B0P7: self-cooled
JZAB1P5: cooling fan
JZA20P1 to 20P4: self-cooled
JZA20P7 to 24P0: cooling fan
JZA40P2 to 40P7: self-cooled
JZA41P5 to 44P0: cooling fan
<1> Instantaneous average deceleration torque refers to the torque required to decelerate the motor (uncoupled from the load) from the rated motor
speed down to zero in the shortest time.
<2> Ensure that Stall Prevention Selection during Deceleration is disabled (L3-04 = 0) or set to 3 when using a braking resistor or the Braking
Resistor Unit. The default setting for the stall prevention function will interfere with the braking resistor.
<3> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<4> Ground protection cannot be provided under the following circumstances when a ground fault is likely in the motor windings during run: Low
ground resistance for the motor cable and terminal block; low ground resistance for the motor cable and terminal block; or the drive is powered
up from a ground short.
A.4 Drive Specifications
166
SIEP C710606 33A OYMC AC Drive – J1000 User Manual