85
Explicit Messages
Appendix C
Command Details
• [CMND S
D
C]
S: D01000
D (first response word): D02000
C: D00000
Contents of S
Contents of C
Response
Contents of D
Address
Contents (Hex)
Meaning
D01000
28 01
Command code
D01001
41 0E
PROFIBUS Communication Unit’s station address: 65
Service code: 0E Hex
D01002
00 9C
Class ID: 009C Hex
D01003
00 01
Instance ID: 0001 Hex
D01004
73
**
Attribute ID: 73
**
Hex (Set any value for the blank boxes.)
Address
Contents (Hex)
Meaning
D00000
00 09
Number of bytes of command data
D00001
00 2A
Number of bytes of response data
D00002
00 00
Destination PROFIBUS Master Unit’s network address: 0
D00003
00 11
Destination PROFIBUS Master Unit’s unit address: 11 Hex
D00004
00 00
Response required
Communication port number: 0
Number of retries: 0
D00005
00 3C
Response monitoring time: 6 s
Address
Contents (Hex)
Meaning
D02000
28 01
D02001
00 00
D02002
00 24
D02003
41 8E
Response source station address: 65 (41 Hex)
Normal completion: 8E Hex
D02004 to D02020
20 00
Number of slave alarm data: 32 (20 Hex)
Status of slave #4, Status of slave #3 (2 bits each)
D02005
00 00
Status of slave #8, slave #7, slave #1, slave #2 (2 bits each)
D02006 to D02020
...
(continue)