65
Wiring Methods
Section 2-4
When using thick cable, provide some slack in the cable so that the con-
nectors do not pull out because of tension on the cable.
Note
The OMRON XW4Z-00C and PHOENIX CONTACT SZF-1 screwdrivers are
suitable for tightening the DeviceNet connector’s set screws. Refer to
2-3
Cables, Connectors, and Related Devices
for contact information to order the
PHOENIX CONTACT screwdriver.
The following diagram shows the dimensions of the XW4Z-00C screwdriver.
Multi-drop Wiring
Methods
Multi-drop Connection with a Standard Connector (Thin Cables Only)
When thin cable is being used, a multi-drop connection can be made by
inserting each pair of wires into a single same pin terminal and crimping them
together.
Note
We recommend using the following PHOENIX CONTACT terminal for this
type of multi-drop connection.
• PHOENIX CONTACT AI-TWIN Series
Multi-drop Connection with a Multi-drop Connector
The following OMRON Multi-drop Connectors (sold separately) can be used
to make a multi-drop connection with either thin or thick cable.
• XW4B-05C4-T-D Straight Multi-drop Connector without Attachment
Screws
Slotted screwdriver that
does not taper at the tip
3.5 mm
0.6 mm
Side
Front
Model
Crimping Tool
AI TWIN2
×
0.5-8WH (for thin cable)
CRIMPFOX UD6
Summary of Contents for DEVICENET -
Page 1: ...DeviceNet Cat No W267 E1 11 OPERATION MANUAL...
Page 2: ...DeviceNet Operation Manual Revised April 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 7: ...viii...
Page 9: ...x...
Page 13: ...xiv...
Page 41: ...20 Basic Operating Procedures Section 1 4...
Page 107: ...86 Operational Checklist Section 2 6...
Page 123: ...102 Step 3 Splitting the System into Multiple Power Supplies Section 3 6...
Page 161: ...140 Index...