16
DeviceNet-compatible Devices
Section 1-2
Note
The Analog Input Units, Analog Output Units, Temperature Input Units, and
Counter Units belong to a group called Special I/O Units. The front-panel indi-
cators and other parts of Special I/O Units differ from those of other I/O Units.
One I/O Unit Connecting Cable (cable length 40 mm) is included with each I/O
Unit. One end connector is attached to the Communications Unit.
I/O Unit Connecting Cables with a cable lengths of 0.1, 0.3, 0.4, 0.6, and 1 m
(GCN1-010/030/040/060/100) are sold separately (see below).
Special
I/O
Units
(See
note.)
Analog
Input
Units
4 inputs
4 words
0 words
M3 terminal
block
24 V DC
(sup-
plied
from
outside)
DIN
track
GT1-AD04
Inputs:
4 to 20 mA,
0 to 20 mA,
0 to 5 V,
1 to 5 V,
0 to 10 V,
–10 to 10 V
8 inputs
8 words
0 words
Connector
(made by
MOLEX)
GT1-AD08MX
Analog
Output
Units
4 outputs
0 words
4 words
M3 terminal
block
GT1-DA04
Outputs:
4 to 20 mA,
0 to 5 V,
1 to 5 V,
0 to 10 V,
–10 to 10 V
4 outputs
0 words
4 words
Connector
(made by
MOLEX)
GT1-DA04MX
Outputs:
0 to 5 V,
1 to 5 V,
0 to 10 V,
–10 to 10 V
Tempera-
ture Input
Unit
4 inputs
4 or 8
words
(varies
with data
format)
0 words
M3 terminal
block
GT1-TS04T
Sensor
types: R, S,
K, J, T, B, L
GT1-TS04P
Sensor
types: Pt100,
JPt100
Counter
Unit
1 input
3 words
3 words
M3 terminal
block
GT1-CT01
1 external
input
2 external
outputs
Unit
I/O
points
Words allocated in
PLC memory
I/O connec-
tions
Unit
power
supply
voltage
Instal-
lation
Model
number
Remarks
Input
Output
0.1 m/0.3 m/0.4 m/0.6 m/1 m
Summary of Contents for DEVICENET -
Page 1: ...DeviceNet Cat No W267 E1 11 OPERATION MANUAL...
Page 2: ...DeviceNet Operation Manual Revised April 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 7: ...viii...
Page 9: ...x...
Page 13: ...xiv...
Page 41: ...20 Basic Operating Procedures Section 1 4...
Page 107: ...86 Operational Checklist Section 2 6...
Page 123: ...102 Step 3 Splitting the System into Multiple Power Supplies Section 3 6...
Page 161: ...140 Index...