4
DeviceNet-compatible Devices
Section 1-2
1-2
DeviceNet-compatible Devices
1-2-1
Master Unit Models
1-2-2
DeviceNet Functions of OMRON Master Units
Remote I/O Master Function
Applicable PLC
Master Unit model
number
Mounting position
Master/Slave
functions
Max. number of Units
With
Configurator
Without
Configurator
CS Series
CS1W-DRM21(-V1)
CPU Rack or Expansion I/O
Rack (Classified as CPU
Bus Units)
Master and
Slave functions
16
CJ Series
CJ1W-DRM21
CVM1, CV Series
CVM1-DRM21-V1
CPU or Expansion CPU
Rack (Classified as CPU
Bus Units)
Master func-
tion only
16
1
CS Series
C200HW-DRM21-V1 CPU Rack or Expansion I/O
Rack (Classified as Special
I/O Units)
16
C200HZ/HX/HG/HE
10 or 16
C200HS
10
DeviceNet
DeviceNet Master Unit
CPU Unit
Remote I/O communications
Slaves
Item
Master
Model
Without Configurator
With Configurator
Max. No. of Slave
nodes per Master
CS Series
CS1W-DRM21(-V1)
63 nodes
CJ Series
CJ1W-DRM21
63 nodes
CVM1, CV Series
CVM1-DRM21-V1
63 nodes
CS Series, C200HX/
HG/HE
C200HW-DRM21-V1
50 nodes
63 nodes
C200HS
32 nodes
63 nodes
Max. No. of control
points per Master
CS Series
CS1W-DRM21(-V1)
2,048 pts (64 input /64
output words) or
16,000 pts (500 input/500
output words)
32,000 pts (500 words x
4 blocks)
CJ Series
CJ1W-DRM21
CVM1, CV Series
CVM2-DRM21-V1
2,048 pts (64 input/ 64
output words)
6,400 (100 words x 4
blocks
CS Series, C200HX/
HG/HE
C200HW-DRM21-V1
1,600 pts (50 input/50
output words)
Without messages:
4,800 pts
With messages:
1,600 pts
C200HS
1,024 pts (32 input/32
output words)
1,280
Summary of Contents for DEVICENET -
Page 1: ...DeviceNet Cat No W267 E1 11 OPERATION MANUAL...
Page 2: ...DeviceNet Operation Manual Revised April 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 7: ...viii...
Page 9: ...x...
Page 13: ...xiv...
Page 41: ...20 Basic Operating Procedures Section 1 4...
Page 107: ...86 Operational Checklist Section 2 6...
Page 123: ...102 Step 3 Splitting the System into Multiple Power Supplies Section 3 6...
Page 161: ...140 Index...