45
Cables, Connectors, and Related Devices
Section 2-3
Communications Cable and Communications Distance
Note
Thin cable includes the cables with shielded connectors attached.
Cable
Max. network
length
Max. branch
line length
Max. total branch line
length
Thick cable
At 500 kbps: 100 m
At 250 kbps: 250 m
At 125 kbps: 500 m
6 m
At 500 kbps: 39 m
At 250 kbps: 78 m
At 125 kbps: 156 m
Thin cable
(See note.)
100 m
Flat cable
At 500 kbps: 75 m
At 250 kbps: 150 m
At 125 kbps: 265 m
6 m
At 500 kbps: 35 m
At 250 kbps: 48 m
At 125 kbps: 135 m
Wire type
Color
Function
Symbol
Signal wires
Blue
Communications signal, Low
CAN L
White
Communications signal, High
CAN H
Power wires
Red
Communications power, positive
V+
Black
Communications power, negative
V
−
Shield wire
---
Shield
S
Conductor
No.
Insulation
color
Application
Nominal
cross-
section
Conductor
resistance
(
Ω
/km)
Allowable
current (A)
1
Red
V+
(communica-
tions power sup-
ply positive side)
0.75 mm
2
(AWG19)
25.0 max.
5 max.
2
White
CAN H
(signal high)
0.5 mm
2
(AWG21)
37.5 max.
---
11.2 mm to 12.1 mm
outside diameter
Woven shield
Shield wire
Signal wires
(Blue and white)
Power wires
(Red and black)
Signal wires
(Blue and white)
Power wires
(Red and black)
Shield wire
Woven shield
6.9 mm outside diameter
Red:
V+
Black:
V
−
White:
CAN H
Blue:
CAN L
Summary of Contents for DEVICENET -
Page 1: ...DeviceNet Cat No W267 E1 11 OPERATION MANUAL...
Page 2: ...DeviceNet Operation Manual Revised April 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 7: ...viii...
Page 9: ...x...
Page 13: ...xiv...
Page 41: ...20 Basic Operating Procedures Section 1 4...
Page 107: ...86 Operational Checklist Section 2 6...
Page 123: ...102 Step 3 Splitting the System into Multiple Power Supplies Section 3 6...
Page 161: ...140 Index...