Warning 

 

Please read this instruction sheet carefully before use and follow this instruction to operate the device in order to 

prevent damages on the device or injuries to staff. 

 

Switch off the power before wiring. 

 

This instruction sheet only provides introductory information on electrical specification, functions, wiring, 
trouble-shooting and peripherals for DVPCP02-H2. Details of CANopen protocol are not included in this sheet. For 
more information on CANopen protocol, please refer to relevant reference or literatures. 

 

DVPCP02-H2 is an OPEN TYPE device and therefore should be installed in an enclosure free of airborne dust, 
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from opearting the device 
(e.g. key or specific tools are required to open thte enclosure) in case danger and damage on the device may occur. 

 

DVPCP02-H2 is to be used for controlling the operating machine and equipment. In order not to damage it, only 
qualified professional staff familiar with the structure and operation of it can install, operate, wire and maintain it. 

 

DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all 
the wiring again before switching on the power, and DO NOT touch any terminal when the power is switched on. Make 
sure the ground terminal 

  is correctly grounded in order to prevent electromagnetic interference. 

 

Introduction

 

Thank  you for choosing Delta DVPCP02-H2 CANopen communication module. DVPCP02-H2 can be applied 

to the connection with DVP-EH2 series PLC MPU on CANopen network. 

 Features 

1. Complies with CANopen standard  protocol 

DS301v4.02 

2. Supports NMT service 

3. Supports SDO service and 1 SDO server 

4. Supports  standard Run/Error indication 

5. Supports PDO service:  Max. 8 TXPDO and 8 RXPDO, 

and supports all PDO transmission  types 

6. Able to detect low voltage 

 Product Profile & Outline 

POWER

ERR

RUN

DR 2
DR 1

IN 0

DR 0

X

16

X

16

2

3

5

4

6

7

8

9

1

G N D

S HL D

CA N -

CA N +

4 0   [1 . 5 7 5 ]

7

  

[0

.2

7

6

]

9

0

  

[3

.5

4

3

]

8 2   [3 . 2 2 8 ]

 

Unit: mm/[inch] 

 

1

 

Extension  port 

4

 

POWER indicator 

7

 

CANopen connector 

2

 

Address switch 

5

 

RUN  indicator 

8

 

DIN rail 

3

 

Function switch 

6

 

ERR indicator 

9

 

DIN rail clip 

ENGLISH 

 Specifications    

CANopen Connector 

Type 

Removable  connector (5.08mm) 

Transmission  method 

CAN 

Transmission  cable 

2 communication cables,  1 grounding cable, 1  shielded cable 

Electrical  isolation 

500V DC 

Communication 

Message  type 

PDO, SDO, SYNC (synchronous  object), Emergency (emergency  object), NMT 

Series  transmission 

speed 

10k, 20k, 50k, 125k, 250k, 500k, 800k, 1M bps (bits  per  second) 

Product  code 

83 

Equipment type 

Company ID 

477 (Delta Electronics, Inc.) 

Electrical Specifications 

Weight (approx.  g) 

130 (g) 

Current 

28mA (typical); impulse  current 125mA (24V DC) 

Voltage 

Supplied by DVP-EH2 MPU 

Environment 

Standards 

IEC 61131-2, UL508 

Noise immunity 

RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1,000MHz, 1.4GHz ~ 2GHz, 10V/m 

EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV 

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 

Storage/operation 

Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution  degree 2 

Storage: -25°C ~ 70°C (temperature); 5 ~ 95% (humidity) 

Shock/vibration 

immunity 

International  standards: IEC61131-2, IEC 68-2-6 / IEC61131-2 & IEC 68-2-27 

Certificates 

CE, UL 

    Components

 

 CANopen Connector 

To connect to CANopen network, use the connector enclosed with DVPCP02-H2 or any connectors you can 
buy in the store for wiring. 

PIN 

Signal 

Description 

GND 

GND 

CAN_L 

Signal- 

SHIELD 

Shielded  cable 

CAN_H 

 

Reserved 

4

G ND

SH LD

C AN-

C AN+

5

3
2
1

 

 Address Switch 

The two rotary address setup switches set up the node addresses on CANopen 
network  in hexadecimal form.   

Rotary switch 

x 16

1

 

x 16

0

 

Multiple 

× 16 

× 1 

 

N

O

D

E

A

D

D

R

E

S

S

x1 6

0

x1 6

1

 

Example: If you need to set the node address of DVPCP02-H2 as 26 (1A Hex), simply switch the 
corresponding  rotary switch  of x16

1

 to “1" and the corresponding rotary switch of x16

0

 to”A”. 

Switch setting 

Description 

0x01

 

~

 

0x7F 

Valid CANopen node  address 

0, 0x80

 

~ 0xFF 

Invalid CANopen node  address 

Note: 

The changed values on switches are only 

valid when DVPCP02-H2 is re-powered. When 
DVPCP02-H2 is operating, changing the set 
value of the address will be regarded invalid.

 

 Function Switch (DIP) 

DR2 

DR1 

DR0 

Baud  rate 

OFF 

OFF 

OFF 

10kbps 

OFF 

OFF 

ON 

20kbps 

OFF 

ON 

OFF 

50kbps 

OFF 

ON 

ON 

125kbps 

ON 

OFF 

OFF 

250kbps 

ON 

OFF 

ON 

500kbps 

ON 

ON 

OFF 

800kbps 

ON 

ON 

ON 

1Mbps 

IN0 is  reserved. 

DR 2
DR 1

IN  0

DR 0

 

Note: Set up the function switch when the power of DVPCP02-H2 is switched off. Re-power DVPCP02-H2 after the 

setup is completed. 

 Extension Port 

The extension port on DVPCP02-H2 is used for the connection to the next DVPCP02-H2 or extension  modules 
of DVP-EH2  series PLC MPU. 

 

Basic Operation

 

 Connecting DVPCP02-H2 to DVP-EH2 Series PLC MPU 

G ND

SHLD

CAN -

CAN+

STO P

R UN

0

1

 

IN

OUT

PO WER

RUN

ERROR

BAT. LOW

DVP-20EH

DR 2
DR 1

IN 0

DR 0

 

Switch off DVP-EH2. Open the connection port on 

the right hand side of DVP-EH2 and  connect 

DVPCP02-H2 to DVP-EH2. Switch on DVP-EH2, 

and DVP-EH2 will supply power to DVPCP02-H2. 

There is no need to connect DVPCP02-H2 to an 

external  power  supply. 

 Installing DVP-EH2 and DVPCP02-H2 on DIN Rail 

STO P

R UN

0

1

 

IN

OU T

PO W ER

RU N

ER RO R

BAT. LOW

D V P - 2 0 E H

DR  2

DR  1

IN  0

DR  0

G ND

SHL D

CAN -

CAN +

 

1.  Use 35mm DIN rail. 

2.  Open the DIN rail clips on DVP-EH2 and 

DVPCP02-H2. Insert DVP-EH2 and 
DVPCP02-H2 onto the DIN rail. 

3.  Clip up the DIN rail clips on DVP-EH2 and 

DVPCP02-H2 to fix DVP-EH2 and DVPCP02-H2 
on the DIN rail, as shown in the figure.

 

 Connecting to CANopen Connector 

G ND

SHLD

C AN-

CAN+

 

 

 Installation & Wiring 

1. Install DVPCP02-H2 in an enclosure with sufficient space 

around it  to allow heat  dissipation (see the figure). 

2. DO NOT place the I/O signal wires and power supply wire 

in the same wiring circuit.

 

D>5 0 mm

CP 02-H 2

D

D

D

D

EH 2 PL C

D

D

 

 

Control Register 

The control registers (CR) are the registers inside DVPCP02-H2. See the table below for the definitions of all 
the CRs. DVP-EH2 series PLC MPU can read or write the CR allowed through DFROM/DTO instructions.

 

CR# 

Attribute 

Content 

High byte 

Low byte 

#0 

Read 

Model name 

DVPCP02-H2 model code = H’0240 

#1 

Read 

Firmware  version 

Displaying the current firmware version in hex, e.g. V1.00 is 

indicated as H’0100. 

#2 

Read 

Length of I/O data 

Length of output I/O data 

Length of input I/O data 

#3 ~ #102 

Read/write  Input data editing area 

DVPCP02-H2 

 data storage area in CANopen master 

#103 ~ #202 

Read/write  Output data editing area  CANopen master 

 data storage area in DVPCP02-H2 

#203 ~ #215 

Set up by the system. DO NOT use it. 

#255 

Read/write 

MPU status 

CR#255 = K0: MPU in STOP status 

CR#255 = K1: MPU in RUN status 

 

LED Indicators & Trouble-Shooting

 

There are 3 LED indicators on DVPCP02-H2. POWER indicator displays the status of working power. RUN and 
ERR indicators display the working status of DVPCP02-H2 on  CANopen network. 

 Indicator Status & Flash Rate 

Indicator status 

Flash  rate 

Steady  on 

Constantly  on 

Blinking 

ISO-phase on and off with a frequency of approximately 2,5 Hz: on for approximately 
200ms followed by off for approximately 200ms. 

Single  flash 

One  short flash  (approximately 200ms) followed by a long off phase (approximately 
1,000ms).

 

Double  flash 

A sequence  of two  short flashes (approximately  200ms), separated  by an off phase 
(approximately 200ms). The sequence is finished by a long off phase (approximately 
1,000ms). 

 POWER LED 

LED status 

Indication 

How to deal with it? 

Off 

No  power 

Check the power of DVPCP02-H2 and see if the 
connection is normal. 

Green  light  steady 
on 

Normal 

-- 

 RUN LED 

LED status 

Indication 

How to deal with it? 

Off 

No  power 

Check the power of DVPCP02-H2 and see if the 
connection is normal. 

Green light  single 
flash 

DVPCP02-H2 in STOP status 

-- 

Green light blinking 

DVPCP02-H2 in 

pre-operational status 

-- 

Green light  steady on 

DVPCP02-H2 in operational 

status 

-- 

 ERR LED

 

LED status 

Indication 

How to deal with it? 

Off 

Normal 

-- 

Red light  single flash 

Bus error  exceeds the  warning 
limit. 

Check if the bus connection is correct. 

Red  light  double flash  Error  control  event 

Check and make sure the bus connection is normal. 

Red light steady on 

Bus-off 

1. Check if the network connection is normal and 

re-power it. 

2. Send it back to the factory for repair if necessary. 

 

注意事項 

 

使用前請務必仔細閱讀本使用手冊,並依照本手冊指示進行操作,以免造成產品受損或人員受傷。

 

 

配線時請務必關閉電源。

 

 

本使用說明書僅提供電氣規格、功能規格、安裝配線、故障排除及周邊裝置部分說明,本使用說明書僅作為

DVPCP02-H2

操作指南和入門參考,

CANopen

協定的詳細內容這裏不作介紹。如果讀者想瞭解更多

CANopen

協定的內容,請參閱相關專業文章或書籍資料。

 

 

本機為開放型機殼,因此使用者使用本機時,必須將其安裝於具防塵、防潮及免於電擊∕衝擊意外的外殼配線
箱內。另必須具備保護措施(如:特殊的工具或鑰匙才可打開),防止非維護人員操作或意外衝擊本體,造成
危險及損壞。

 

 

本產品用來控制運轉中的機械及設備。為避免損壞本產品,只有合格且熟悉本產品結構及操作的專業人員才
可進行本產品的安裝、操作、配線及維護。

 

 

交流輸入電源不可連接於輸入∕輸出信號端,否則可能造成嚴重損壞。請在上電前再次確認電源配線,且請
勿在上電時觸摸任何端子。本體上的接地端子

 

 

務必正確的接地,以提高產品抗雜訊能力。

 

 產品簡介

 

謝謝您使用台達

DVPCP02-H2

網路通訊模組。

DVPCP02-H2

定義為

CANopen

通訊模組,可用於

CANopen

網路

DVP-EH2

系列

PLC

主機的連接。

 

 

功能特色

 

1.

 

符合

CANopen

標準協定

DS301v4.02

 

2.

 

支援

NMT

服務。

 

3.

 

支援

SDO

服務,支援

1

SDO

伺服器功能。

 

4.

 

支援標準

Run /Error 

指示。

 

5.

 

支援

PDO

服務:最大支援

8

TXPDO

RXPDO

支援所有的

PDO

傳輸類型。

 

6.

 

提供本機

LV

偵測。

 

 

產品外觀及各部介紹

 

POWER

ERR

RUN

DR 2
DR 1

IN 0

DR 0

X

16

X

16

2

3

5

4

6

7

8

9

1

G N D

S HL D

CA N -

CA N +

4 0   [1 . 5 7 5 ]

7

  

[0

.2

7

6

]

9

0

  

[3

.5

4

3

]

8 2   [3 . 2 2 8 ]

 

尺寸單位:

mm/[inch]

 

1

  擴充模組連接埠 

4

 

POWER

指示燈 

7

 

CANopen

通訊連接器 

2

  位址設定開關 

5

 

RUN

指示燈 

8

 

DIN

軌槽 

3

  功能設定開關 

6

 

ERR

指示燈 

9

 

DIN

軌固定扣 

繁體中文 

 

功能規格

 

CANopen

連接器

 

接頭 

可插拔式連接  (

5.08mm

傳輸方式 

CAN

 

傳輸電纜 

2

條通訊線、

1

條接地線、

1

條遮罩線 

電氣隔離 

500V DC

 

通訊

 

資訊類型

 

PDO

SDO

SYNC

(同步物件)、

Emergency

(緊急物件)、

NMT 

串列傳輸速度

 

支援

10k

20k

50k

125k

250k

500k

800k

1M bps

(位∕秒)

 

產品代碼

 

83 

設備類型

 

廠商

ID 

477

(台達電子)

 

電氣規格

 

重量

  (

, g) 

130 (g) 

電流規格

 

28mA

(典型值);衝擊電流

125mA (24V DC) 

電源電壓

 

DVP-EH2

主機提供電源

 

環境規格

 

標準

 

IEC 61131-2

UL508

標準

 

雜訊免疫力

 

RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1,000MHz, 1.4GHz ~ 2GHz, 10V/m 
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV 

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 

操作∕儲存環境

 

操作:

0°C ~ 55°C

(溫度),

50 ~ 95%

(濕度),污染等級

  2 

儲存:

-25°C ~ 70°C

(溫度),

5 ~ 95%

(濕度)

 

耐振動∕衝擊

 

國際標準規範

  IEC61131-2, IEC 68-2-6 / IEC61131-2 & IEC 68-2-27 

認證專案

 

CE

認證、

UL

認證

 

    各部分元件介紹

 

 

CANopen

通訊連接器

 

CANopen

網路連接時,可使用

DVPCP02-H2

隨機附帶的連接器或市售的連接器進行配線。

 

引腳

 

信號

 

說明

 

GND 

GND 

CAN_L 

Signal- 

SHIELD 

遮罩線

 

CAN_H 

 

保留

 

4

G ND

SH LD

C AN-

C AN+

5

3
2
1

 

Reviews: