131
Appendix
A-4
Error Messages - System
The table below lists the Error messages related to the System on which the DTM is installed.
52
CX-Server could not be config-
ured
Configuration of CX-Server failed.
• Make sure the settings within the
Device Set-up tab are correct.
Select the Test Button to check
this.
• Make sure the Personal Com-
puter COM port selected within
the Device Set-up Configuration
is not in use by another applica-
tion. If it is close the connection
from within the other application.
• Restart CX-PROFIBUS.
• Restart Personal Computer to
ensure COM port is released.
• Ensure the correct version of CX-
Server is installed on the Personal
Computer. Refer to the Master
Manual for installation details.
When the problem has been
removed, perform one of the fol-
lowing successfully to confirm the
problem has been solved:
* Select the Configure Button in
the Device Set-up tab
* Select the Test Button in the
Device Set-up tab
53
CX-Server could not be initialized
Initialization of CX-Server was not
possible.
• Ensure the correct version of CX-
Server is installed on the Personal
Computer. Refer to the Master
Manual for installation details.
Number
Message
Description
Correction
100
Connected device can not be con-
figured with this DTM
Incorrect firmware type.
Make sure the unit connected is a
CS1W-PRM21 or CJ1W-PRM21.
Make sure the Unit number in the
Device set-up corresponds to the
physical unit.
101
Incorrect version of CX-Server.
Incorrect version of CX-Server.
Make sure the correct CX-Server
version is installed. Version must be
1.7 and up.
102
[Name of the function] called with
improper parameters
Container called a function with
NULL pointer.
There must be problem in the con-
tainer. Reinstall CX-PROFIBUS, if
problem persists contact supplier.
103
Received XML Document does
not fit it's XML schema
Container called a function with an
improper XML document.
There must be a problem in con-
tainer program. Reinstall CX-PROFI-
BUS, if problem persists contact
supplier.
104
Ole Register Drop Target Failed
An internal error has occurred.
Reinstall CX-PROFIBUS, if problem
persists contact supplier.
105
Undefined control type
An internal error has occurred.
Reinstall CX-PROFIBUS, if problem
persists contact supplier.
106
Communication failure with the
DTM
An internal error has occurred.
Reinstall CX-PROFIBUS, if problem
persists contact supplier.
107
GUI could not be closed
An internal error has occurred.
Reinstall CX-PROFIBUS, if problem
persists contact supplier.
Number
Message
Description
Correction