129
Appendix
02
PROFIBUS I/O Data exceeds
memory range
Input / Output area exceeds memory
range (combination of start address
and length).
Change the configuration to be
within the memory area and retry
download.
03
Slaves should have unique
addresses
Unique bus addresses must be
assigned for each slave.
Change the addresses of the slaves
and ensure no duplicates are
present. Retry download.
04
DTM cannot be added to the net-
work, it is not a PROFIBUS device
DTM
The slave DTM cannot be con-
nected, e.g. if adding HART device
DTM.
Avoid using non-PROFIBUS DP
DTMs.
05
Max. number of slaves configured.
New slave cannot be added
DTM can not be added, since the
master has already the maximum
number of slaves (125) assigned.
Do not add any more DTMs. If more
are still needed, a second PROFI-
BUS Master Unit on the same PLC
system may be solution.
06
Slave address overlap detected.
New address assigned: [new
address]
Changing the address of an existing
slave results in an address overlap.
Automatically recovers.
07
Invalid data set received from a
slave DTM. Slave parameter
changes ignored
An internal error has occurred pre-
venting the master DTM to obtain
the slave's parameter set.
Add a new slave DTM into the net-
work (or change the modules of the
existing slave) with correct slave
parameter set.
08
Set Parameters failed. Slave can-
not be configured
An internal error has occurred pre-
venting the master DTM from set-
ting/changing the slave's bus
address.
Non recoverable. Master DTM tries
to assign a new bus address to the
slave DTM, but the slave DTM’s
database is locked.
09
No slaves assigned. Download
aborted
No slaves have been assigned to the
master. At least one slave must be
assigned.
Retry download when at least one
slave has been assigned.
10
Slave(s) has no modules. Down-
load aborted
A slave (or slaves) has no modules.
Retry download when modules have
been added to the slave(s) having
no modules.
11
Configured EM bank (banks) is
not available in the connected
PLC.Download aborted
The configured EM bank (banks) are
not available in the connected PLC.
Change the configuration to use only
memory areas available in the PLC
and retry download.
12
Connected unit is busy. Download
aborted
Unit is busy with parameter storage. Retry download when parameter
storage has finished.
13
Slave configuration too big
The total number of configured
parameter bytes and configuration
bytes does not fit into the FINS mes-
sage for downloading.
Reduce the configuration.
14
Maximum number of modules
exceeded
The total number of configured I/O
modules over all allocated slave
devices can not exceed 4000.
Do not add any more modules to the
configuration.
15
PROFIBUS Master is not in cor-
rect mode. Please set the PROFI-
BUS Master in one of the following
modes: STOP, CLEAR or OPER-
ATE.
The Set Device Station Address
command can not be executed
because the PROFIBUS Master is
not in correct mode, i.e. the Master
Unit is OFFLINE.
Set the PROFIBUS Master into one
of the following modes: STOP,
CLEAR or OPERATE.
16
Master Unit indicated failure of Set
Device Station Address.
When sending Set Device Station
Address command, one of the fol-
lowing problems occurred:
• The slave has deactivated this
service.
• The slave has not responded to
the request.
• The slave does not have sufficient
memory space for the request
data.
• Check target Slave device on the
PROFIBUS network.
• Check specified Slave address.
• Check Slave timeout parameter
17
'New address' and/or 'Ident num-
ber (hex)' are/is empty.
No data is entered in the New
Address and Ident Number fields.
Fill-in both the 'New address' and the
'Ident number (hex)' fields.
Number
Message
Description
Correction