![background image](http://html1.mh-extra.com/html/omron/cx-profibus-1-0/cx-profibus-1-0_operation-manual_744199102.webp)
87
Configuring the Master
Section 3-4
3-4-4
Configuring CX-Server
Configuring
Communication
The CS1/CJ1W-PRM21 Master DTM uses CX-Server to connect to the Unit
for both downloading a configuration as well as monitoring the Master Unit. In
order to setup the communication to the Unit, perform the following proce-
dure.
1,2,3...
1.
Open the CS1/CJ1W-PRM21 Master DTM Configuration Interface, Device
Setup tab.
2.
Make sure that the Unit Number has been set to the unit number set on the
PROFIBUS Master Unit, through the rotary switch on the front.
3.
Select the
Configure
button to start CX-Server.
CX-Server
Up on pressing the
Configure
button, CX-Server is launched and displays the
CX-Server User Interface as shown below.
Configuring CX-Server
In order to configure CX-Server for communication with the Unit, perform the
following procedure.
1,2,3...
1.
Select the type of PLC to which the Unit is attached, from the
Device Type
drop down selection box.
2.
Press the
Settings
button next to the PLC type selected. The PLC settings
window (see figure below) is displayed.
3.
In this window make the proper adjustments if necessary. The selections
made, must match the physical configuration of the PLC system. When
done, press the
OK
button.