A-4 CP1L Programming Examples
160
SYSMAC CP1L Getting Started Guide
Ap
pend
ix
A-4-9 Exchanging Data between CP1Ls
Functions Used
z
Simple PLC Link
By using RS-422A/485 option boards, up to 10CH of data per CPU unit can be shared
by as many as 9 CP1L/CP1H/CJ1M units, without the aid of a program.
Operation Overview
Current temperature information is exchanged by boilers.
This setup may be used to adjust boiler temperatures according to the other boiler
conditions, or to monitor the boilers from a single location.
System Configuration
z
Wiring Example
Boiler A
Boiler B
Boiler C
1CH,2CH
Temperature sensor unit
CP1W-TS101
2 Pt100 sensor inputs
CP1W-CIF11
(RS422/485 option board)
1CH,2CH
2 Pt100 sensor inputs
CP1W-CIF11
(RS422/485 option board)
1CH,2CH
2 Pt100 sensor inputs
CP1W-CIF11
(RS422/485 option board)
1
CP1W-CIF11
2
4
5
RDA–
3
RDB+
SDA–
SDB+
FG
Simple PLC link
1
CP1W-CIF11
2
4
5
RDA–
3
RDB+
SDA–
SDB+
FG
1
CP1W-CIF11
2
4
5
RDA–
3
RDB+
SDA–
SDB+
FG
Boiler A: CP1L (Master)
Boiler B: CP1L (Slave No.0)
Boiler C: CP1L (Slave No.1)
Temperature sensor unit
CP1W-TS101
Temperature sensor unit
CP1W-TS101
RDA
- RDB+ SDA
- SDB+ FG
COMM
RDA
- RDB+ SDA
- SDB+ FG
COMM
RDA
- RDB+ SDA
- SDB+ FG
COMM