A
A-4 CP1L Programming Examples
SYSMAC CP1L Getting Started Guide
161
Ap
pend
ix
z
DIP Switch Setup for CP1W-CIF11 (RS422/485 Option Board)
z
PLC Setup
Configure serial port 1.
1.
Open the PLC Settings dialog box.
2.
Click the Serial Port 1 tab.
3.
Set the following settings.
No.
Setting
Master
Slave
No.0
Slave
No.1
Content
1
Presence of terminating
resistance
ON
OFF
ON
Terminating resistance present
for PLCs at the ends.
2
2/4-wire selection
ON
ON
ON
2-wire type
3
2/4-wire selection
ON
ON
ON
2-wire type
4
-
OFF
OFF
OFF
Always OFF
5
RS control for RD
OFF
OFF
OFF
Disabled
6
SD control for RD
ON
ON
ON
Enabled
CPU unit connector
Operation setup
DIP switches