1. Attach the MX2 inverter to the filter using the M4 screws (4 off) supplied with the
filter.
2. Attach a suitable 230VAC mains supply to the terminal block of the filter, ensuring
that the earth is securely connected to the stud to the left of the terminal block,
using a crimp-on eyelet. For MX2-AB002-E (0.25kW) and MX2-AB004-E (0.4kW)
models, AWG16/1.3mm
2
cable should be used. For the MX2-AB007-E (0.75kW)
model, AWG12/3.3mm
2
cable should be used. (See section 2-3-6 of User’s Manual
I570-E2-01 for further details and fuse protection recommendations.)
3. The filter includes captive AC supply cables which should be connected accordingly
to the L1 (Live) and N (Neutral) screw terminals of the MX2 inverter, as shown in
the diagram on the previous page. The Earth wire is terminated into an eyelet
which should be attached to the leftmost M4 chassis ground screw. (See section 2-
3-11 of User’s Manual I570-E2-01 for further details.)
4. If used, connect the motor to the MX2 inverter in accordance with the wiring
instructions in section 2-3-12.
5. Perform the pre-check and power-up tests as detailed in section 2-4.
Serial communication connection between the MX2 inverter and PLC:
The MX2 inverter will be controlled entirely by MODBUS commands over the RS485 serial
communication link (to the CP1L PLC), so no ‘hard’ I/O wiring is required.
Your Lean Automation Kit will have been supplied with a 2m twisted-pair cable which fits
between the ‘SN’ and ‘SP’ terminals of the MX2 and the screw terminals of the CP1W-
CIF11 RS422/485 communications option module, fitted in the right-hand slot of the CP1L
PLC.