Mounting the C200HW-CORT21
Section 2-2
27
2-2
Mounting the C200HW-CORT21
The C200HW-CORT21 can be mounted to the CPU Rack or Expansion I/O
Rack of any CS1, C200HX, -HG, or -HE PLC. Refer to the PLC’s Operation
Manuals for details on mounting Units.
Limitations
There are some limitations on mounting the Unit.
•
The current consumption of all Units mounted on one backplane should
not exceed the maximum output of the power supply. The C200HW-
CORT21 consumes up to 250 mA from the 5V supply. Verify the
characteristics of all other Units on their respective Instruction Sheets.
•
The C200HW-CORT21 is a Special I/O Unit. It can be mounted in any
slot in the backplane of a CPU Rack or Expansion I/O Rack as long as
its Unit number is not the same as the Unit number of another Special
I/O Unit within the system.
•
The maximum number of Special I/O Units that can be mounted depends
on the PLC CPU type.
•
For details on CS1-series PLC compatibility, see Appendix A.
CPU Unit models
Max. number of
Special I/O Units
C200HE,
C200HG-CPU3
❏
-E/CPU4
❏
-E,
C200HX-CPU3
❏
-E/CPU4
❏
-E
10
C200HG-CPU5
❏
-E/CPU6
❏
-E,
C200HX-CPU5
❏
-E/CPU6
❏
-E/CPU8
❏
-ZE
CS1-series
16
2-3
Network cabling
All devices are connected in a bus structure (i.e. line). The wiring topology of
a CAN network should be as close as possible to a single line structure in
order to avoid cable-reflected waves. Stub-lines should be kept as short as
possible and must be less than 30 cm at the highest baud rate (1 Mbit/s).
Summary of Contents for C200HW-CORT21
Page 1: ...C200HW CORT21 CAN Unit OPERATION MANUAL Cat No W904 E2 1...
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ...C200HW CORT21 CAN Unit Operation Manual Produced July 2000...
Page 6: ...iv...
Page 8: ...vi...
Page 10: ...viii...
Page 12: ...x...
Page 24: ...Performance Section 1 3 22...
Page 40: ...LEDs 7 Segment Display Section 3 3 38...
Page 56: ...Maintenance Section 5 3 54...
Page 58: ...56...
Page 60: ......