Physical layout of the Unit
Section 2-1
26
BR2
BR1
BR0
Baud rate (kbit/s)
OFF
OFF
OFF
10
OFF
OFF
ON
20
OFF
ON
OFF
50
OFF
ON
ON
125
ON
OFF
OFF
250
ON
OFF
ON
500
ON
ON
OFF
800
ON
ON
ON
1000
Note
The C200HW-CORT21 enables to configure any arbitrary baud rate via the
Unit settings. Refer to section 3-1-1 for the definition of these Unit settings.
2-1-5
BUS Connector
The fieldbus connector is a 5-pin male open style connector. The pins are
numbered 1 to 5 starting from the top. The label besides the connector
indicates the colour of the individual wire in the cable that has to be
connected to the respective pin.
The C200HW-CORT21 requires external power for the transceiver and opto-
couplers. Therefore 24V DC
±
10% must be connected to pin 1 and 5.
Pin No.
Signal
Description
1
CAN_V+
CAN external positive supply for powering the
transceiver and opto-couplers.
2
CAN_H
Data signal (dominant high)
3
CAN_SHLD
Optional CAN shield
4
CAN_L
Data signal (dominant low)
5
CAN_GND
Ground