![Omniflex C1180 User Manual Download Page 90](http://html1.mh-extra.com/html/omniflex/c1180/c1180_user-manual_739283090.webp)
Omni8/16C/Omni8P User Manual
UMC1480R24.pdf
90
© Omniflex 2021
Sequence 27 - Momentary (Fleeting) Alarm, Auto Reset, for Motor Alarms (Timer option off)
STATE 2
STATE 3
STATE 4
STATE 1
RETURN
TO
NORMAL
ABNORMAL
HORN OFF
1 2 3 4 5 6 7 8
ON
SEQUENCE SWITCH
SETTING
LAMP OFF
HORN OFF
SIL
LAMP FAST
FLASH
HORN OFF
LAMP FAST
FLASH
HORN ON
ACK WHILE
ABNORMAL
ACK WHILE
NORMAL
LAMP SLOW
FLASH
ACK
WHILE
NORMAL
ACK WHILE
ABNORMAL
Sequence 27 - Momentary (Fleeting) Alarm; Auto Reset; for Motor Alarms; with Time Delay on Inputs
RETURN TO
NORMAL
ABNORMAL
LAMP ON
1 2 3 4 5 6 7 8
ON
SEQUENCE SWITCH
SETTING
HORN OFF
STATE 1
STATE 5
STATE 2
STATE 3
STATE 4
RETURN TO
NORMAL
LAMP OFF
HORN OFF
TIMER OFF
LAMP OFF
HORN OFF
TIMER
RUNNING
TIME OUT
LAMP FAST
FLASH
HORN ON
TIMER OFF
SIL
LAMP FAST
FLASH
HORN OFF
TIMER OFF
ACK
HORN OFF
TIMER OFF
T
ACK WHILE ABNORMAL
LAMP SLOW
FLASH
ACK WHILE
NORMAL