Omni8/16C/Omni8P User Manual
UMC1480R24.pdf
57
© Omniflex 2021
CONFIGURATION OPTION
DIP SWITCH
SET MODE
SOFT-SET
MODE
Setup Group Alarm 1 to 4 Type
If a relay output has been configured as a GA output, then the
GA operation can be set-up for one of the following:
GA follows input
GA follows alarm
GA acts as ring back
GA set to multiple reflash
GA follows ACK pushbutton (not available in switchset
mode)
Yes
GA1 RL 3 only
Yes
Lamp Sense
Setup Lamp Sense
All Lamps Normal Sense or Lamps Reversed Sense.
Note: This setting only applies when SW1-8 is ON.
Yes
Yes
Split First Out Group
First Out Group Split
Enter a number between 1 and 16 to decide the split between
First Out Group 1 and 2. For example: A value of 4 will arrange
input 1 to 4 into First Out Group 1 and inputs 5 to 16 into First
Out Group 2.
No
Single group of 16
Yes
System Operation
Various System functions can be setup as follows:
Pushbutton Edge/Level Detection (default: edge)
Auto ACK on Startup i.e. Turn off running light sequence
(default is ON)
Inhibit Input operation i.e. Close or Open to Inhibit (default
is Close to Inhibit) Note: Only applies when SW1-8 is ON.
Repeat Relay Output Options:
Follows Input, Normally Open
Follows Input, Normally Closed (Default)
Follows Alarm, Normally Open
Follows Alarm, Normally Closed
Acts as GA output
No
No
Yes
No
Yes
Yes
Yes
Yes
5.3
Selecting the Input Sense
There is an 8 way “set-up” switch associated with each group of eight inputs. These are used to set the
sense of the eight input contacts – normally open or normally closed.
These switches are located directly above each group of eight input terminals on the rear of the
Omni8/16C and are clearly marked.