Omni8/16C/Omni8P User Manual
UMC1480R24.pdf
49
© Omniflex 2021
4.12.5
Controlling multiple Omni8C/16C’s with an Omni8P Alarm Annunciator
Up to 16 Omni8/16C units may be controlled as part of a single alarm system using an Omni8P Alarm
Unit. Wire the pushbuttons of all units in parallel as shown below:
The Pushbuttons of the Omni8P will control all of the connected units.
Figure 4-13 – Omn8P Annunciator controlling multiple Omni8C/16C units.
4.13
Connecting the C1415 Remote Pushbutton Station
Omni8/16C units may be controlled by a single Remote Pushbutton Station C1415. Simply wire as shown
below.
Terminal Strip D
Pushbuttons
11
12
13
14
15
Teminal Strip
3
4
Terminal Strip D
RL2 set as Horn O/P
SIL
RESET
ACK
TEST
C COM
O.C.
+24Vdc
COM
RES
ACK
SIL
TST
GND
OC
1
2
Terminal Strip C
24V Terminals
+24V
0V
OMNI8C/16C
C14xx
Remote Pushbutton
Station C1415
Internal Buzzer
Figure 4-14 – Connecting C1415 Remote Pushbutton Station to Omni8/16C units.
Terminal Strip
D
11
12
13
14
15
COM
RES
SIL
ACK
TEST
Terminal Strip
D
11
12
13
14
15
COM
RES
SIL
ACK
TEST
Terminal Strip
D
11
12
13
14
15
COM
RES
SIL
ACK
TEST
Omni8P
(has Integral Pushbuttons)
Omni8/16C
No. 2
Omni8/16C
No. 16