![Omniflex C1180 User Manual Download Page 59](http://html1.mh-extra.com/html/omniflex/c1180/c1180_user-manual_739283059.webp)
Omni8/16C/Omni8P User Manual
UMC1480R24.pdf
59
© Omniflex 2021
Table 5-3 – The Sequence Switch Settings
SEQUENCE SWITCHES
SW1
SW2
SEQ.
NO.
1 2 3 4
5 6 7 8 1 2 3 4 5 6 7 8
DESCRIPTION
ISA
DESIGNATION
T
TIME DELAY ON...
0
0 0 0 0
0
0 0 0 0 0
FACTORY TEST MODE
1
1 0 0 0
0
1 0 0 0 0
LAMP FOLLOWS INPUT
--
--
2
0 1 0 0
0
0 1 0 0 0
MOMENTARY (FLEETING) ALARM, MANUAL RESET
M-1
INPUTS
3
1 1 0 0
0
1 1 0 0 0
ALARM ONLY (NO LOCK-IN) AUTO RESET
A-1-4
INPUTS
4
0 0 1 0
0
0 0 1 0 0
MOMENTARY ALARM, MANUAL RESET WITH RINGBACK
R-1-10
INPUTS
5
1 0 1 0
0
1 0 1 0 0
MULTIPLE GROUP, FIRST OUT MANUAL RESET
F2M-1
--
6
0 1 1 0
0
0 1 1 0 0
FIRST OUT, AUTO RESET, F.O. RESET INTERLOCK
F3A-1-3
--
7
1 1 1 0
0
1 1 1 0 0
SINGLE GROUP, 1st OUT, MANUAL RESET, 1st UP CONTINUOUS FLASH
--
--
8
0 0 0 1
0
0 0 0 1 0
1st OUT, MANUAL RESET WITH NO SUBSEQUENT ALARM STATE SILENCE PUSHBUTTON
F1M-1
INPUTS
9
1 0 0 1
0
1 0 0 1 0
MOMENTARY (FLEETING) ALARM MANUAL RESET
--
HORN
10
0 1 0 1
0
0 1 0 1 0
MOMENTARRY (FLEETING) ALARM MANUAL RESET
--
REFLASH
11
1 1 0 1
0
1 1 0 1 0
MOMENTARY (FLEETING) ALARM MANUAL RESET FOR MOTOR ALARMS
--
INPUTS
12
0 0 1 1
0
0 0 1 1 0
MOMENTARY (FLEETING) ALARM
--
RETURN TO NORMAL
13
1 0 1 1
0
1 0 1 1 0
PULSE MONITORING ALARM WITH MANUAL RESET
--
--
14
0 1 1 1
0
0 1 1 1 0
MOMENTARY (FLEETING ALARM), MANUAL RESET, WITH RINGBACK.
18
0 1 0 0
1
0 1 0 0 1
MOMENTARY (FLEETING) ALARM AUTO RESET
--
INPUTS
21
1 0 1 0
1
1 0 1 0 1
MULTIPLE GROUP, FIRST OUT, AUTO RESET
F2A-1
--
23
1 1 1 0
1
1 1 1 0 1
SINGLE GROUP, 1st OUT, AUTO RESET, 1st UP CONTINUOUS FLASH
--
--
24
0 0 0 1
1
0 0 0 1 1
MULTIPLE GROUP, FIRST OUT, AUTO RESET, NO SUBSEQUENT ALARM STATE, SILENCE PUSHBUTTON
F1A-1
--