![Omniflex C1180 User Manual Download Page 102](http://html1.mh-extra.com/html/omniflex/c1180/c1180_user-manual_739283102.webp)
Omni8/16C/Omni8P User Manual
UMC1480R24.pdf
102
© Omniflex 2021
Holding /
Input Reg.
Coil /
Input
Status
DIT No.
Description
Read/
Write
231
N/A
230
Setup System Operation
Bit 0: Pushbutton Edge/#Level:
1 – Edge, 0 – Level
Bit 1: Auto ACK on Startup:
1 – NO Auto ACK on Startup, 0 - Auto ACK on Startup
Bit 2: Inhibit Input operation:
1 – Close to Inhibit, 0 – Open to Inhibit
Note: This setting only applies when SW1-8 is ON.
Bit 3-5: Repeat Output operation:
The bit map is as follows:
Bit 5:4:3: 1:1:1 – Repeat Relay Follows Input, Normally Open
Bit 5:4:3: 1:0:1 – Repeat Relay Follows Input, Normally Closed (default)
Bit 5:4:3: 1:1:0 – Repeat Relay Follows Alarm, Normally Open
Bit 5:4:3: 1:0:0 – Repeat Relay Follows Alarm, Normally Closed
Bit 5:4:3: 0:0:0 – Repeat Relay Acts as GA
Bit 6-15: Reserved
R/W
232
N/A
231
Setup Slow Timer
The slow timer counts in multiples of the fast timer. This is configurable to allow the most flexible use of timers.
Some examples are given below:
To count in seconds:
set to 10
To count in 10s of seconds:
set to 100
To count in 20s of seconds:
set to 200
R/W