![Omniflex C1180 User Manual Download Page 80](http://html1.mh-extra.com/html/omniflex/c1180/c1180_user-manual_739283080.webp)
Omni8/16C/Omni8P User Manual
UMC1480R24.pdf
80
© Omniflex 2021
Sequence 2 - Momentary (Fleeting) Alarm Manual Reset with Time Delay on Inputs
RESET WHILE
NORMAL
ABNORMAL
LAMP ON
1 2 3 4 5 6 7 8
ON
SEQUENCE SWITCH
SETTING
HORN OFF
STATE 1
STATE 5
STATE 2
STATE 3
STATE 4
RETURN TO
NORMAL
LAMP OFF
HORN OFF
TIMER OFF
LAMP OFF
HORN OFF
TIMER
RUNNING
TIME OUT
LAMP FAST
FLASH
HORN ON
TIMER OFF
SIL
LAMP FAST
FLASH
HORN OFF
TIMER OFF
ACK
LAMP ON
HORN OFF
TIMER OFF
T
ACK
Sequence 3 - Alarm Only (No Lock-in), Auto Reset, (Timer option off)
STATE 4
STATE 3
RETURN TO
NORMAL
ABNORMAL
LAMP ON
HORN OFF
1 2 3 4 5 6 7 8
ON
SEQUENCE SWITCH
SETTING
STATE 2
STATE 1
LAMP OFF
HORN OFF
SIL
ACK
LAMP FAST
FLASH
HORN OFF
LAMP FAST
FLASH
HORN ON
ACK
RETURN TO NORMAL
RETURN
TO
NORMAL
Sequence 3 - Alarm Only (No Lock-in) Auto Reset with Time Delay on Inputs
RETURN TO
NORMAL
ABNORMAL
1 2 3 4 5 6 7 8
ON
SEQUENCE SWITCH
SETTING
STATE 1
STATE 5
RETURN TO
NORMAL
LAMP OFF
HORN OFF
TIMER OFF
LAMP OFF
HORN OFF
TIMER
RUNNING
TIME OUT
SIL
ACK
T
ACK
STATE 4
LAMP ON
HORN OFF
TIMER OFF
STATE 2
LAMP FAST
FLASH
HORN ON
TIMER OFF
RETURN TO NORMAL
LAMP ON
HORN OFF
STATE 3
LAMP FAST
FLASH
HORN OFF
TIMER OFF