OMNI 4000/7000 Operations and Maintenance Guide
– Rev F
7-30
Maintenance
3.
Use the
Up
or
Down
arrow keys to scroll
through the list of output channels.
4.
Press the
Cancel
function key to abort the
calibration process or press
OK
or the
Accept
function key to select the
highlighted channel.
5.
Connect an ammeter in series between
the flow computer and the external
4
‒20 mA device.
6.
Press the
Start
function key to begin the
calibration process.
7.
Confirm that the next screen shows the
Output Value (mA)
field default of 4.00.
8.
Wait 20 to 30 seconds for the readings to
stabilize.
9.
Note the value indicated on the ammeter.