C.3 Digital Binary (dry-contact, switches) Sensor Interface P/N DIG_DIY1
The Digital binary 1/0 is a common industrial signal that indicates ON/OFF states of machines,
motors, valves, open/close doors, and more. The
Datalog X-PRO Digital Two Inputs Binary
Interface (DIG-DY1)
easily takes digital states, counts the quantity of events, and can be
programmed to send an alert when a detected state changes.
C.3.1 D.C. Electrical Characteristics
PARAMETER
Ratings
Supply Voltage from Datalog X-PRO
3.3 VDC
Supply Output Current to a Dry Contact
0.33mA
Maximum Output Voltage
3.3VDC
C.3.2 Specifications
PARAMETER
Operational Range
Temperature
41°F – 104°F (5°C to 40 °C)
Relative humidity
25-75 %
Resolution
1 bit
Digital Conversion Range
0 or 1
C.3.3 Connection Diagram
Figure C3-1 Digital Binary (dry-contact, switches) Sensor Interface *
* 10K Pull-Up Resistor supplies a current of 0.33 mA to polarize and detect the dry contact or
switch state.
www.omicroning.co March 2020