7.0 TROUBLESHOOTING
SYMPTOM
POSSIBLE ORIGIN
SOLUTION
A) Temperature
shown in display
higher than the preset
value.
•
High compressed air inlet temperature.
•
High compressed air flow.
•
High ambient temperature.
•
Fouler refrigerant condenser.
•
Low refrigerant charge.
•
Phases connected incorrectly.
•
Faulty refrigerant compressor.
•
Faulty fan.
•
Faulty fan pressure switch or thermostat.
•
Faulty electronic controller
•
Problems with circulator cabling.
•
Glycol circulator defective.
•
Glycol leakage.
•
Reduce air temperature to within design limits.
•
Reduce air flow to within design limits.
•
Increase ventilation rate of installation area.
•
Clean condenser.
•
Locate and repair leak and re-charge.
•
Connect the phases correctly.
•
Replace item.
•
Replace item.
•
Replace item.
•
Replace item.
•
Check cabling.
•
Replace circulator.
•
Check glycol circuit and connections, if necessary
replace flexible tubes and/or refill glycol tank to
correct level.
B) Excessive air
pressure drop across
dryer.
•
Inlet / outlet piping reversed.
•
Temperature probe out of well.
•
Faulty refrigerant solenoid valve.
•
Ambient temperature below freezing.
•
Obstruction in air circuit.
•
Air by – pass valve close.
•
Connect properly.
•
Re-install.
•
Replace item.
•
Install dryer in heated space.
•
Locate and remove blockage.
•
Open valve.
C) Water present in air
downstream of dryer.
•
Condensate drain strainer fouled.
•
Faulty condensate drainer.
•
Faulty electronic controller.
•
High dew – point temperature.
•
Air by – pass valve open.
•
Clean strainer.
•
Replace item.
•
Replace item.
•
See Symptom #A above.
•
Close valve.
8.0 CONDENSATE DRAIN
8.1 Drain valve maintenance
•
Close the ball valve located on the filter/stop installed at the drain trap inlet.
•
Depressurize the trap by pushing the TEST button on the control panel.
•
Unscrew the plug in the end of the filter/stop to access the filter screen (F)
and clean it with a compressed air jet.
•
Reassemble and open filter/stop valve.
Cleaning of the drain
solenoid valve
1= Dicharge endurance (3 sec)
2=
Interval between
discharges (2 min)
8.2 NO LOSS CONDENSATE DRAIN
(F)
Summary of Contents for ESD 1300
Page 2: ...1 119...
Page 4: ...5 119...
Page 87: ...RU OMI 1 ON OFF 12...
Page 88: ...1 0 1 1 OMI 5 IP 42 1 2 1 2 3 4 5 6 7 8 9...
Page 90: ...HFC 3 0 3 1 OMI 0 C 50 C 90 12 OMI 3 2 40 1000 3 3 1 2 3 4 5 10...
Page 91: ...4 0 1S1 ON OFF 3 3 5 0 5 1 5 2 5 3 6 6 0 SET POINT 1 DEW POINT...
Page 92: ...6 1 HP LP CO14 6 2 ON 6 3 3 ON OFF OFF SET POINT...
Page 93: ...6 4 15 1 ALrM 2 ALOG 3 C1Hr 4 Hot Key UPL 6 5 6 5 1 P2 P3 P4 6 5 2 1 2 AlrM 3 rSt NO 4 rSt rSt...
Page 101: ...7 0 A B 0 C A...
Page 103: ...8 3 TEST 9 0 10 0 R134a R407C R507 15 15 11 0 EN378 1...
Page 122: ......