background image

OMEGA | OMEGA-VSHP.F-PGD-1904 

 

 

 

 

 

 44     

www.omega-heatpump.com   

1 GENERAL 

Install Omega series Vertical Stack Heat Pumps as indicated on 
the plans and capacities listed in the schedule and specifications.  

Each unit shall be factory tested and ship factory-charged with R-
410A refrigerant. All units from 1/2 to 3 Tons shall be tested and 
certified by ASHRAE/ANSI/AHRI/ ISO 13256-1 and ETL listed for 
United States and Canada.  Each unit shall have factory affixed 
label showing ASHRAE/ANSI/AHRI/ISO and ETL logos. Cabinets 
and refrigeration chassis shall be factory wired and pre-piped. 

2 CABINET 

2.1 

The vertical stacked heat pump units shall be Omega 

(Gold) or (Silver) Series. Units shall provide scheduled capacities at 
the ampacity and voltage specified. 

2.2 

The cabinet shall be 20-gauge galvanized steel with 

riveted internal components for rigidity. Cabinet shall have internal 
surfaces insulated with 1 inch thick, 3.5 lbs. high-density, mould 
resistant, thermal and acoustic insulation. Insulation shall meet 
NFPA 90, UL-181, and ASTM-C1071 standards and insulation shall 
have a flame spread of less than 25, and a smoke developed clas-
sification of less than 50 per ASTM E-84 and UL 723. 

 

(STANDARD SILVER UNIT) The unit shall be a single cabinet 
construction. Contractor shall be responsible for isolating the 
supply duct and supply grille from the cabinet. 

 

(OPTIONAL GOLD UNITS) The cabinet shall be sectionalized 
for acoustic and installation purposes. The lower section shall 
include the risers, blower and fan motor assembly, all con-
trols, and removable refrigeration chassis. The upper section 
shall be an acoustic discharge plenum lined with 1 inch thick, 
3.5 lbs. high-density, mould resistant, thermal and acoustic 
insulation. The discharge plenum shall be designed to be 
fastened to the underside of the concrete slab with field cut 

”Knockout” discharge openings. There shall be no rigid con-

nection between the upper and lower cabinet sections. A 
factory supplied flexible canvas connection shall be provided 
between the upper and lower sections joined by factory pro-

vided “S” and “D” cleats. Heat pump manufacturer shall 

factory attach flexible connection to the plenum section. 
Installing contractor shall make the final connection of the 
flexible connection to the lower cabinet section with field 

provided sheet metal screws and factory supplied “S” and 
“D” cleats. 

 

2.3 

A removable inner chassis service panel allowing ser-

vice access to the fan and compressor compartment shall be pro-
vided with each unit.  

2.4 

The drain pan shall be 16-gauge stainless steel. The 

drain pan shall come standard with a condensate overflow switch. 
The drain pan outlet shall be readily accessible for cleaning with a 
7/8 inch OD copper drain connection. Unit shall be provided with a 
flexible p-trap condensate hose for connection to the condensate 
riser. 

2.5  

Factory installed supply and return risers shall be (Type 

L) (Type M) copper, with (factory) (field) mounted shut-off ball 
valves on each supply and return riser. Valves shall be brass and 
rated for 400 psig. A (Type M/DWV) condensate riser shall be 
(factory) (field) installed. Risers sizes shall be installed according to 
building plans.  

2.6  

Risers shall be factory swaged. Transition pieces shall 

be field supplied. 

2.7 

Unit cabinet shall come with supply discharge opening 

“knockouts”. 

An optional noise attenuating insulated privacy air 

baffle (LOSB) shall be provided for horizontal supply discharge 
openings. All cabinet discharge openings shall include 1-1/2 inch 
drywall flange around the full opening perimeter. Supply ducts 
shall not be rigidly attached to the cabinet and shall be acoustically 
isolated from cabinet using flexible canvas connections. 

2.9 

Each unit shall have an (Acoustic) (Perimeter) return air 

panel. The panels shall be insulated with 1/2 inch thick, lined 
fiberglass insulation. The panel shall be easily removable without 
tools to allow access to the filter, chassis compartment and 
(optional) service disconnect switch. 

3 FAN & BLOWER 

3.1  

Each unit shall include a factory mounted forward 

curved, double inlet double width centrifugal direct drive fan and 
motor assembly with internal overload protection. The blower fan 
assembly shall be positioned horizontally from a sheet metal blow-
er deck.  

3.2  

Units shall be supplied with a 3 speed PSC fan motor 

with permanent split capacitor or ECM fan motor. Fan motors 
speeds shall be field selectable using unit mounted 3-speed fan 
switch or by 3-speed thermostat.  

4 REFRIGERATION CHASSIS 

4.1.  

Provide high temperature and pressure rated water 

hoses for connection of the risers to the chassis. The hoses sup-
plied shall be constructed with an inner core of rubber, a stainless-
steel metal braid, and rubber outer covering. Fittings shall be brass 
construction. Hoses shall carry a pressure rating of 600 psig. 

4.2.  

The compressor chassis shall be mounted and vibration-

ally isolated on 12-gauge slide rails using a double isolated base. 
Compressor shall have an acoustical enclosure ensuring compres-
sor noise is isolated from air stream. Provide plug type electrical 
connections for chassis control and power connections allowing for 
easy removal of the chassis from the front of the cabinet.  

4.3  

The refrigeration circuit shall have two service valves, 

for measuring high and low refrigerant pressure, in the chassis 
compartment enclosure. The refrigerant circuit shall contain a 
thermal expansion valve (TXV) refrigerant metering device and a 
reversing valve. 

4.4 

Compressor shall be hermetically sealed type with inter-

nal thermal overload protection. Compressor shall be mounted on 
rubber vibration isolators. 

4.5 

Air side coils shall have copper tubes mechanically 

10. SPECIFICATIONS 

Summary of Contents for VSHP SERIES

Page 1: ...OMEGA VSHP SERIES Product Guide VERTICAL STACKED WATER SOURCE HEAT PUMPS MODEL VSHP DEV F DOCUMENT RELEASE OMEGA VSHP F PGD 1904 Issue Date April 2019...

Page 2: ...Openings 17 5 3 Top Supply Discharge Openings with Optional Fresh Air Duct 18 5 4 Line of Sight Baffle 19 5 5 Acoustic Front Return Air Panel Furring Details 20 5 6 Perimeter Front Return Air Panel Fu...

Page 3: ...e Installation The equipment is shipped to site in two stages for inte gration with the phases of construction This avoids po tential issues with storage and on site damage and allows mechanical units...

Page 4: ...abinet Compressor elastomeric isolation mounts Unit base with closed cell foam isolation pads Optimized design of refrigerant piping for reduced compressor noise Gold Series Enhanced Acoustic Package...

Page 5: ...omega heatpump com 3 1 3 Heat Pump Operation Schematic Figure 1 Cooling Mode Flow Diagram Figure 2 Heating Mode Flow Diagram Cooling Heating EAT Entering Air Temp LAT Leaving Air Temp EWT Entering Wa...

Page 6: ...ngs in Left Right Front Back and or Top configurations Openings are not available on the same side as mounted risers DX Coil Air to refrigerant coils are multi row with copper tubes and enhanced alumi...

Page 7: ...rge differential pressure range of 2 80 psig 3 80 psig for VSHP 080 to 120 units Condensate Overflow Switch COFS Condensate overflow switch float switch or electronic is mounted to the unit drain pan...

Page 8: ...base section contains all the components and top section is a supply discharge plenum attached to base section using the factory provide flex duct connector The plenum is mounted to the ceiling struct...

Page 9: ...h Outside Air Duct Figure 4 Optional Fresh Outside Air Duct Note Handing is referenced by facing the unit return air opening front OA Fresh Outside Air Intake CAUTION The introduction of cold conditio...

Page 10: ...oded View 2 4 Assembly View Knockout style supply air openings Front Back Side Supply Return and Condensate Risers Direct driver blower motor assembly Electrical Box w Microprocessor Controller Chassi...

Page 11: ...he blower housings with rubber isolation fasten ers which reduces the vibration pro duced by the rotating fan assembly Flex Duct Isolator Units with the optional Gold Series option feature a flexi ble...

Page 12: ...ge 3 CABINET DIMENSIONAL INFORMATION 3 1 Standard Silver Series Cabinet Figure 7 Silver Series Dimensional Drawing Model Cabinet Size Dimensions in W D VSHP 020 X 16 18 5 VSHP 030 VSHP 040 VSHP 050 Y...

Page 13: ...MEGA VSHP F PGD 1904 OMEGA www omega heatpump com 11 Drawing not to scale dimensions are subject to change 3 2 Optional Gold Series Cabinet with Acoustic Plenum Figure 8 Gold Series Dimensional Drawin...

Page 14: ...ered from factory with 3 inch deep swage Contractor to provide riser transition pieces when joining dissimilar riser sizes Risers available in sizes 3 4 to 3 Consult factory for larger sizes All handi...

Page 15: ...insert 2 inches into the 3 inch swage connection Riser Length Floor Clearance Height Slab Thickness 2 inch overlap Rounded up to 120 or 144 Omega supplies two standard riser lengths 120 10 and 144 12...

Page 16: ...1904 14 www omega heatpump com 4 3 Riser Stub Outs Figure 12 Riser Stub Distance from Cabinet Wall Figure 11 Riser Stub Out Opening Detail Side View Note Back Rear Risers are centered to the cabinet...

Page 17: ...e Riser Installation shown Figure 13 Hose Kit Details Riser Shut off Valve w MNPSM Male Thread Soldered to Riser Tee Flexible Hose w FNPSM Female Thread Chassis Connection w MNPSM Male Thread Model Ho...

Page 18: ...Knockout Discharge Opening Figure 14 Standard Knockout Style Openings Units comes with standard Knockout style discharge openings for field configuration This allows for custom discharge configuration...

Page 19: ...rn air opening A discharge option if applicable is not available on the side of the unit where risers are mounted Figure 15 Supply Discharge Openings 5 2 Supply Discharge Openings Model VSHP Supply Di...

Page 20: ...r fresh air duct location Figure 16 Supply Air Opening Sizes with OA in Horizontal Vertical Configurations Table 5 Supply Air Opening Sizes w Fresh Air Duct W D Horizontal Vertical VSHP 020 12 x 10 8...

Page 21: ...nside discharge plenums on units with 2 two or more horizontal discharge openings The LOSB provide occupant privacy between adjacent rooms Two configura tions LSB LR or LSB RL of LOSB are available ba...

Page 22: ...ernal surface for enhanced sound attenuation Return air panel supplied in standard powder coat white finish custom finishes available consult colour chart Model Cabinet Size Acoustic RA Panel Dimensio...

Page 23: ...ulation Right Riser Location Left is Mirror Back Riser Location Figure 19 Acoustic Panel Furring Detail Top View 5 5 Acoustic Front Return Air Panel Furring Details Cont d Figure 20 Acoustic Panel Cab...

Page 24: ...fied by customer based on base board height total flooring thickness Base board must be at least 0 5 smaller than C 54 1 4 Table 7 Acoustic Panel Rough In Dimensions 5 5 Acoustic Front Return Air Pane...

Page 25: ...on for enhanced sound attenuation Return air panel supplied in standard powder coat white finish custom finishes available consult colour chart Model Cabinet Size Perimeter RA Panel Dimensions inches...

Page 26: ...rance at the back side of the units Insulate the drywall enclosure with plenum rated acoustical insulation 5 6 Perimeter Front Return Air Panel Furring Details Cont d Figure 23 Perimeter Panel Cabinet...

Page 27: ...ht total flooring thickness Base board must be at least 0 5 smaller than C Calculate finished floor thickness as part of baseboard height requirement 58 1 2 Table 9 Perimeter Panel Rough In Dimensions...

Page 28: ...9 1 3 2 8 13 7 16 43 25 VSHP 100 208 230 1 60 1 13 5 72 5 1 2 3 6 17 1 20 48 30 VSHP 120 208 230 1 60 1 15 4 83 9 3 4 5 0 20 4 24 25 35 VSHP ECM Qty RLA LRA HP FLA VSHP 020 208 230 1 60 1 3 0 15 0 1 4...

Page 29: ...OMEGA VSHP F PGD 1904 OMEGA www omega heatpump com 27 6 2 Wiring Diagram Standard PSC Motor 208 230 277V 1Ph 60Hz...

Page 30: ...OMEGA OMEGA VSHP F PGD 1904 28 www omega heatpump com 6 3 Wiring Diagram Optional ECM 208 230 277V 1Ph 60Hz RED...

Page 31: ...ssor On O B Reversing Valve C Common On Heat Cool Thermostats Y Cooling O B Heating Note Factory supplied 6 wire 24 inch thermostat cable coiled up in low voltage compartment of electrical box for fie...

Page 32: ...GPM AIR FLOW SCFM WPD ft w c BTUH WATT EER BTUH WATT COP VSHP 20 R410 208 230 60 1 1 5 200 3 3 5800 475 12 20 7200 491 4 30 VSHP 30 R410 208 230 60 1 2 6 350 11 0 8900 712 12 50 11900 758 4 60 VSHP 4...

Page 33: ...91 345 17 45 7829 60 52 1 6346 480 3 91 4716 1 7 4 7 69 3 6795 4661 331 18 57 7936 54 3 6540 474 4 07 4882 2 1 7 1 67 7 6849 4717 319 19 39 8047 55 2 6696 445 4 41 4994 2 5 10 0 66 5 6858 4774 308 20...

Page 34: ...285 1 3 3 0 70 87 7 9287 6679 675 14 48 11533 70 56 5 11277 747 4 43 8750 1 8 5 6 82 9 9461 6744 654 15 26 11629 59 9 11673 753 4 55 9111 2 4 9 8 79 8 9636 6838 623 16 25 11709 62 1 12061 759 4 66 947...

Page 35: ...70 87 5 12240 8830 783 15 86 14845 70 57 2 13967 907 4 50 10868 2 4 5 7 82 5 12536 8974 741 17 08 15003 60 5 14491 913 4 64 11357 3 3 10 6 79 1 12692 9094 712 18 09 15080 62 8 14949 920 4 76 11804 3 5...

Page 36: ...97 11055 851 19 80 18923 70 60 4 16998 1046 4 76 13443 3 5 11 4 80 9 16165 11137 828 20 71 19005 62 1 17401 1052 4 85 13834 3 8 13 3 80 0 16199 11159 821 20 95 19015 62 7 17530 1054 4 88 13947 4 14 7...

Page 37: ...7 18851 13877 1097 17 01 22601 70 57 6 21597 1443 4 38 16679 3 9 12 4 81 7 19244 14111 1041 18 29 22804 61 0 22468 1460 4 52 17493 4 13 0 81 4 19270 14127 1038 18 38 22817 61 2 22523 1461 4 53 17544 5...

Page 38: ...3 4 3 0 70 86 6 23222 15905 1506 15 89 28253 70 57 5 27890 1929 4 23 21334 4 9 6 0 81 7 23790 16175 1421 17 26 28562 60 8 29153 1955 4 36 22500 6 5 10 2 78 8 24181 16442 1359 18 28 28733 62 8 30071 19...

Page 39: ...4 4 3 4 2 70 85 7 27762 20307 1786 15 46 33736 70 57 5 34996 2439 4 21 26790 6 1 8 6 81 2 28298 20613 1715 16 35 34060 60 9 36115 2451 4 31 27848 6 5 9 9 80 5 28390 20671 1707 16 47 34131 61 4 36273 2...

Page 40: ...5 8 0 70 86 8 37718 26083 2568 15 78 46321 70 57 5 45380 3230 4 11 34436 7 12 2 83 4 38384 26375 2490 16 55 46750 59 9 46517 3253 4 20 35448 8 15 5 81 7 38706 26509 2448 16 96 46953 61 0 47080 3265 4...

Page 41: ...00 1 013 0 553 0 762 0 971 1 010 1 365 S 70 1 077 1 003 1 058 0 639 0 845 0 883 1 257 1 440 75 1 180 1 006 1 145 0 639 0 680 1 039 1 252 55 0 770 0 989 0 878 1 038 S S S S S 66 2 1 000 1 000 1 000 0 5...

Page 42: ...1 01 1 03 1 00 1 01 1 01 0 99 1 01 110 1 02 1 06 1 01 1 02 1 02 0 98 1 02 115 1 03 1 09 1 01 1 03 1 02 0 98 1 03 Antifreeze Correction Factors Glycol Type Glycol COOLING HEATING Total Cooling Capacity...

Page 43: ...Limits Cooling Heating DB WB DB Std Entering Air Temperature EAT 75o F 63o F 68o F Min Entering Air Temperature EAT 65o F 55o F 50o F Max Entering Air Temperature EAT 85o F 71o F 80o F Fluid Limits St...

Page 44: ...350 338 315 HIGH 600 550 520 500 380 310 050 370 530 LOW 560 510 475 450 MED 645 585 550 505 460 415 HIGH 765 715 670 630 585 530 455 060 410 630 LOW 560 510 475 450 MED 645 585 550 505 460 415 HIGH...

Page 45: ...640 620 610 595 580 565 555 540 525 510 490 475 460 HIGH 675 670 655 650 640 620 610 595 580 565 550 WHISPER M ODE N A N A N A 620 580 560 520 480 440 410 380 340 300 260 LOW 800 760 740 720 695 660...

Page 46: ...all be provided with a flexible p trap condensate hose for connection to the condensate riser 2 5 Factory installed supply and return risers shall be Type L Type M copper with factory field mounted sh...

Page 47: ...he con troller board terminals Thermostats shall be either A Manual changeover low voltage for cooling and heating opera tion Sub base shall have system Heat Off Cool and fan On Auto switches B Automa...

Page 48: ...Omega has a policy of continuous product improvement and reserves the right to change design specifications without notice OMEGA Heat Pumps 3325A Orlando Dr Mississauga ON L4V 1C5 T 905 670 2269 F 905...

Reviews: