Figure 22
Perimeter Panel Furring Drawing
Right Riser Location
(Left is Mirror)
Back Riser Location
Notes:
The framing should be installed for a maximum 0.5” maximum clearance between the heat pump return air flange and the return a
ir
panel throat opening flange.
Return air panel should be centered in front of the unit return air opening.
For rear/side risers, allow an additional 5” clearance at the back/side of the units.
Insulate the drywall enclosure with plenum rated acoustical insulation.
5.6 Perimeter Front Return Air Panel & Furring Details (Cont’d)
Figure 23
Perimeter Panel Cabinet Base Height Calculation
Perimeter Panel Cabinet Base Height Calculation
C
= Cabinet Base Height -
.875”
B
= Bas Finish Floor Height*
G
= Baseboard Gap (min 0.5”)
B
= Cabinet Base Size
(Min 5", increases in 1" increments)
B = B + G + 0.875”
Note: *Include flooring thickness, underlayment, and any
concrete leveling as part of calculation.
Example:
If using a 5" baseboard, with 1” Flooring height, and 0.5" gap
B = (5” + 1”) + (0.5) + 0.875” = 7.375"
Hence an 8" Cabinet Base is required