OMEGA | OMEGA-VSHP.F-PGD-1904
42
www.omega-heatpump.com
9. FAN & MOTOR DATA
9.1 PSC Motor Data
Note: Please call customer service for external static pressure requirements exceeding
0.5”
w.g.
Model
Min.
SCFM
Rated
SCFM
Speed
External Static Pressure (in w.g.)
0
0.1
0.2
0.3
0.4
0.5
0.6
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
020
150
200
LOW
285
230
210
195
160
-
-
MED
320
270
250
225
200
160
-
HIGH
430
355
340
315
280
240
185
030
210
350
LOW
275
235
220
-
-
-
-
MED
310
275
250
230
-
-
-
HIGH
405
370
350
315
280
235
-
040
270
460
LOW
340
300
275
-
-
-
-
MED
410
370
350
338
315
-
-
HIGH
600
550
520
500
380
310
-
050
370
530
LOW
560
510
475
450
-
-
-
MED
645
585
550
505
460
415
-
HIGH
765
715
670
630
585
530
455
060
410
630
LOW
560
510
475
450
-
-
-
MED
645
585
550
505
460
415
-
HIGH
765
715
670
630
585
530
455
080
270
820
LOW
785
735
700
655
615
570
-
MED
855
790
750
710
670
615
-
HIGH
895
840
790
745
710
645
600
100
640
1010
LOW
895
855
790
745
670
-
-
MED
1045
970
925
855
785
710
-
HIGH
1155
1075
1010
935
845
775
670
120
740
1200
LOW
1155
1080
1015
950
875
790
-
MED
1170
1095
1025
970
890
800
-
HIGH
1225
1150
1080
1000
935
850
760
Note: All airflow ratings are taken at lowest voltage rating of dual rating (ie. 208 volt).