OMEGA-VSHP.F-PGD-1904 | OMEGA
www.omega-heatpump.com
29
6.4 Thermostat Wiring Details
Heat Pump Thermostat Connec-
tion Detail
R = 24VAC
G1 = Fan Speed 1
G2 = Fan Speed 2
G3 = Fan Speed 3
Y = Compressor On
O/B = Reversing Valve
C = Common
On Heat/Cool Thermostats
Y = Cooling
O/B = Heating
Note:
Factory supplied 6-wire 24 inch thermostat cable coiled up in low-
voltage compartment of electrical box for field wiring to thermostat.
Field Supplied 7
-
Wire
thermostat cable shown
(used with 3
-
speed
thermostat). Factory
provided 6
-
wire is not
wired to terminal G3.
Figure 28
Thermostat Wiring Detail