4.8.3 Device Setting and Configuration
Make sure that the Receiver is configured (using web access, see
Figure 4.17
) to the
settings below.
TCP Connection = any value from 1 to 5
Port number = 2000 (other values may be acceptable as long as Mail Notifier is setup
with the same Port number).
Then on the Mail Notifier Alarm Editor:
1) Set the "IP address" (for example
192.168.1.200
).
2) Specify "Socket Number"
2000.
3) Set the "Address/RS485 Unit" to the Device ID number for a Connector/Transmitter.
4) Set the "Reading Cmd" using general commands in the Table below.
5) Define the Alarm Configuration (High/Low, High value, or Low value).
Specify Email Interval. This determines how many seconds each subsequential
alarm notification will be sent.
Determine Monitor interval. This establishes the interval or time resolution in
seconds for which readings will be obtained from the device.
Table 4.2 Mail Notifier Commands
Desired Value to Monitor
Reading Cmd string
Actual Command String
(see Note 2)
Reading A
zRdgA
ERDB003
Reading B
zRdgB
ERDB003
Reading C
zRdgC
ERDB003
Battery voltage (mV)
zBatt
EQPE003
Signal Level
zSignal
EQPE003
1. The devices are configured in Mail Notifier with symbolic commands rather
than actual device commands.
2. zRdgA with RS485 Device Unit # as 3, for example, is sent as ERDB003.
3. "Reading A" will be the first value returned for a device in response to a
command such as ERDB003.
40