12

Chapter  7   Specifi cations

ENVIRONMENTAL:

OPERATING TEMPERATURE

   -4°F (-20°C) to  + 158°F (70°C)

  Extended Temp:  -22°F  (-30°C) to + 158°F (70°C)

HUMIDITY

  0 - 90% Noncondensing

MOUNTING STYLES:

1

- Panel Mount -  

NEMA 4X Front

2

- Wall Mount -  

NEMA 4X Enclosure

   

 (keypad mounted behind clear cover)

3

- Explosion Proof - 

Class I, Division I, Groups B, C & D

   

Class II, Division I, Groups E, F & G

INPUTS:

MAGNETIC PICKUP INPUT

  Frequency Range: 0 to 3500 Hz 

  Trigger Sensitivity: 30 mV p-p (10 mV p-p on special order)

  Over Voltage Protected: ± 30 VDC

OPTO-ISOLATED DC PULSE INPUT

  High (logic 1): 4-30 VDC

  Low (logic 0): Less Than 1 VDC

  Minimum Current: .5 mA

  Hysteresis: 0.4 VDC

  Frequency Range: 0 to 5 kHz  

  Min. Pulse Width: 0.1 msec

CONTACT CLOSURE INPUT (contact closure to common)

  Internal Pullup Resistor: 100 KΩ to +3.6 VDC

  High (logic 1): Open or 4-30 VDC

  Low (logic 0): Less Than .5 VDC

  Internal Switch Debounce Filter: 0 to 40 Hz

NOTE

:   Sustained contact closure will shorten 

   

battery life.

RESET INPUT (contact closure to common)

  Internal Pullup Resistor: 100 KΩ to +3.6 VDC

  High (logic 1): Open or 4-30 VDC

  Low (logic 0): Less Than .5 VDC

  Minimum On : 25 msec

NOTE

:   Sustained contact closure will shorten 

   

battery life.

K-FACTOR

  Range: 0.001 to 99999999

  Decimal Point Locations: XXXX.XXXX to XXXXXXXX

20 POINT LINEARIZATION -LIN OPTION

  This  feature  allows  the  user  to  enter  20  different  frequencies 

with 20 different corresponding K-Factors to linearize non linear 

signals.

ANALOG OUTPUT -MA OPTION:

  Type: 4-20 mA follows rate display, Two wire hookup

  Accuracy: 0.025% Full Scale at 20° C

  Temperature Drift:  50 ppm/°C Typical

  Reverse Polarity Protected

  Update Rate: 8 times/second

NOTE:

 The DPF500 uses the 4-20 mA loop power as its primary 

power source when this option is used.  The battery is still 

required for standby battery operation.

DATA STORAGE:

  Setup Information: Stored in fl ash memory

  Totalizer:  Stored  in  battery  backed  RAM  but  can  be  saved  to 

fl ash memory by operator for recall after battery change out.

7.1 Specifi cations

Power:

BATTERY POWERED

  Supplied with 1 or 2 C size Lithium battery pack.

EXTERNAL POWER INPUT

  Voltage: 8.5 to 30 VDC

  Current: Less than 5 mA

  Supplied with 1 C size lithium battery

  Protection: Reverse Polarity Protection on DC Power Input

LOOP POWERED

  Voltage: 8.5 to 30 VDC

  Supplied with 1 or 2 C size lithium battery(ies)

  Protection: Reverse Polarity Protection on Current Loop

  Loop Burden: 8.5V maximum

BATTERY LIFE EXPECTANCY:

Expected Years of Operation for DPF500 of various powering op-

tions at equipment duty cycles

MODEL

RUN TIME

 

Idle 

2hrs/day 

8hrs/day  24hrs/day

-BAT*  

10 yrs 

10 yrs 

10 yrs 

9.1 yrs 

-BAT-LIN 

10 yrs 

10 yrs 

10 yrs 

8.4 yrs

Standard unit   10 yrs 

10 yrs 

10 yrs 

10 yrs

and -MA
(standby-operation)
Standard unit   Indefi nite operation when externally powered
and -MA
External or loop power

* -BAT option contains DPF5-BP battery pack

NOTE:

  Battery shelf life is rated at 10 years by manufacturer

 

Life expectancy based on rated battery capacity at 20°C

 

The above table is shown with pulse output inactive. Use 

of pulse output shortens battery life.

 

Example: A pulse output of 0.06 sec. duration, once per 

second, would derate the battery life by 20%. 

 

DISPLAY:

Rate Display: (selectable decimal)

  5 Digits (99999), 0.35" High, Display updates once per second 

with battery power, 8X per second with DC or Loop power

  Rate Descriptors:  

/SEC, /MIN, /HR

  Min. Input Frequency: 0.01 Hz to 10 Hz (selectable delay of 0.1 

to 99.9 seconds)*

  Selectable Rate Display Damping

Totalizer Display:  (selectable decimal)

  8 Digits (99999999), 0.2" High

  Totalizer Descriptors:   GAL, LIT, FT3, M3,  "blank" 

    

Warning Displays: Low battery warning

PULSE OUTPUT:

  The pulse output advances with the least signifi cant digit of the 

totalizer or decimal multiples there of (see Pulse scale divider).

  Type: Isolated photomos relay

  Max. voltage (off state): 30 VDC

  Current (on state): 100mA

  Pulse Duration: Selectable 0.5, 0.25, 0.125, 0.0625 seconds

  Pulse Scale divider (Pulscale): User selectable, ÷1, ÷10, ÷100 

or OFF

  NOTE: Select OFF for max. battery life.

ACCURACY

:

  0.01% Reading, ±1 count

  Temperature Drift: 50 ppm/°C Worst Case

*  A large delay setting and internal math operations may delay the update rate.

-BAT*  

10 yrs 

10 yrs 

10 yrs 

9.1 yrs 

Summary of Contents for DPF500 Series

Page 1: ...omega com e mail info omega com For latest product manuals omegamanual info DPF500 Series Ratemeter Totalizer Shop online at User sGuide...

Page 2: ...78280 Guyancourt France TEL 33 0 1 61 37 2900 FAX 33 0 1 30 57 5427 Toll Free in France 0800 466 342 e mail sales omega fr Germany Austria Daimlerstrasse 26 D 75392 Deckenpfronn Germany TEL 49 0 7056...

Page 3: ...nsions 3 2 4 Wiring 4 2 5 Typical Applications Wiring Diagrams 4 Chapter 3 20 Point Linearization Operation 3 1 20 Point Linearization LIN option 5 Chapter 4 Programming 4 1 Explanation of Display Pro...

Page 4: ...ii THIS PAGE INTENTIONALLY BLANK...

Page 5: ...Optically Isolated Displays Rate Total Simultaneously 5 Digit Rate Display 8 Digit Totalizer Display 4 20mA Analog Output MA option Powered From Internal Battery or 4 20 mA Output Loop MA option 20 P...

Page 6: ...its end of life A descriptor BAT illuminates when the battery voltage falls below this predetermined value The low bat tery detector operates correctly with all power options The battery or batteries...

Page 7: ...emove cover and 4 panel screws Terminals are on bottom side of PC board Panel Screws 4 92 125 TOP VIEW PANEL INSTALLED 4 63 117 3 4 NPT 2 HLS 5 00 127 5 16 4 25 108 5 25 133 E M 5 00 127 To access ter...

Page 8: ...owmeter with DC Pulse Output Strip Char t Recorder 24 VDC Power Supply ISOLATED INPUT 4 20mA LOOP POWERED NOTE Separate power supplies are recommended to isolate output from input If isolation is not...

Page 9: ...the number of decimal locations allowable in the rate and total to acceptable ranges Press the key to move the decimal Press the E key to select the displayed decimal location NOTE For best performan...

Page 10: ...n GAL BBL MCF M3 blank Press the key to select the descrip tor Press the E key to enter the selected descriptor r sCale ratemeter scaling Sets the rate readout Choose rate per hour Hrs minutes nnIn or...

Page 11: ...divider may be needed so that the pulse output does not exceed the maximum rate of the pulse output If the pulse output pulses too quickly a ashing display will result Pressing the M key will result...

Page 12: ...y to step the factor decimal to the desired location Press the E key to enter the displayed decimal location Press the M key to skip and keep the existing location NOTE For best performance and resolu...

Page 13: ...s the value This will only display on units with Analog Output key to advance to the next digit Press the E key to enter the displayed value Press the M key to skip and keep the existing value Press t...

Page 14: ...ommon To reset the unit from the front panel the following key sequence is required Press M CLr tot will be displayed if the panel lock is on the display will prompt ent code Enter the proper code to...

Page 15: ...gital milliamp meter DMM in series with the analog output and simulating a full scale or over range ow rate If the output is out of calibration perform the following Remove power and or disconnect bat...

Page 16: ...r BATTERY POWERED Supplied with 1 or 2 C size Lithium battery pack EXTERNAL POWER INPUT Voltage 8 5 to 30 VDC Current Less than 5 mA Supplied with 1 C size lithium battery Protection Reverse Polarity...

Page 17: ...therwise shall not exceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequential incidental or special damages CONDITIONS Equipment sold...

Page 18: ...ty Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps Industrial...

Reviews: