![background image](http://html1.mh-extra.com/html/omega/cn8200-series/cn8200-series_user-manual_737605022.webp)
35
Integral
0 to 9600 Seconds
Derivative
0 to 2400 Seconds
Cycle Time
200 ms; 1 to 120 sec
Control Hysteresis
1 to Span of Sensor
Autotune
Operator Initiated from
Front Panel
Manual Control
Operator Initiated from
Front Panel
Mechanical Characteristics
Display
Dual, 4-digit 0.36" (9.2 mm)
LED display
Process Value: Orange
Setpoint Value/Menu: Green
Numeric Range
-1999 to 9999
Front-Panel Cutout
1.771" x 1.771"
(45 mm x 45 mm)
Depth Behind Panel
3.937" (100 mm)
Front Panel Rating
NEMA 4X
Operating Temperature
32 to 140° F (0 to 60° C)
Humidity Conditions
90% R.H. max.,
non-condensing
Parameter Retention
Solid-state, non-volatile
memory
Connections
Input and output via barrier
strip with locking terminals
Contacts
Twin bifurcated
Technical
Specifications
34
Technical
Specifications
Operating Limits
Ambient Temperature
32°F to 140°F (0°C to 60°C)
Relative Humidity Tolerance 90%, Non-Condensing
Power
100 to 250 V
50/60 Hz (Single-Phase)
100 to 250 Vdc
24 Vac/dc
Power Consumption
Less than 6 VA
Performance
Accuracy
±0.20% of Full Scale
(±0.10% Typical), ±1 Digit
Setpoint Resolution
1 Count / 0.1 Count
Repeatability
±1 Count
Temperature Stability
5 µV /°C (Maximum)
TC Cold-End Tracking
0.05°C /°C Ambient
Noise Rejection
>100 dB Common Mode,
>70 dB Series Mode
Process Sampling
10 Hz (100 ms)
Control Characteristics
Setpoint Limits
Automatically Adjust to
Selected TC/RTD
Alarms
Adjustable for High/Low;
Selectable Process, Deviation,
or Band Alarms
Proportional Band
1 to Span of Sensor