25
Output Menu
Display Parameter
Selection
Output 1 Alarm Action
(Latching)
(Normal)
Output 1 Alarm Operation
(Process Low)
(Process High)
(Inverse Band)
(Normal Band)
(Deviation Low)
(Deviation High)
Output 1 Alarm Delay
0-9999 sec
Output 1 Alarm Inhibit
0-9999 sec
Output 1 Alarm Setpoint
Span of Sensor
Output 2 Alarm Action
(Latching)
(Normal)
Output 2 Alarm Operation
(Process Low)
(Process High)
(Inverse Band)
(Normal Band)
(Deviation Low)
(Deviation High)
Output 2 Alarm Delay
0-9999 sec
Output 2 Alarm Inhibit
0-9999 sec
Output 2 Alarm Setpoint
Span of Sensor
Note: The Control
Menu does not apply to
an Alarm Output Type;
therefore, the Control
Menu does not appear.
Alarm Output Type
24
Notes On Alarms
Four types of alarms are available: Process, Deviation,
Inverse Band, and Normal Band. All alarms may be
configured to be inhibited on power-up for a configurable
time duration.
Process Alarm:
Activates at preset value,
independent
of setpoint. “High” process alarm
activates at and above alarm setting.
“Low” process alarm activates at and
below alarm setting.
Deviation Alarm:
Activates at a preset
deviation
value
from setpoint. “High” or “Low” deviation
alarm activates above or below setpoint
according to the preset deviation value.
Inverse Band Alarm: Activates when the process is
within
a specified band centered around the
setpoint.
Normal Band Alarm: Activates when the process
exceeds
a specified band centered around the
setpoint.
Latching Alarms
The Series CN8200’s alarms may also be configured as
latching alarms by selecting
in the Alarm Action
parameter selection.
Deviation, Inverse
Band, and Normal
Band Alarms track
with setpoint.
When a latching alarm
has been activated and
the alarm condition has
been removed, the
Mode/Enter
key
must be pressed to
unlatch the alarm.