34
SCALING THERMOCOUPLE AND RTD(Pt100) INPUT RANGES
Example:
Program a J thermocouple for 50 to 500
°
F
Input Type
Minimum/Maximum Range
J Thermocouple
32 . . . . . . . . . . . . .1472
°
F
Program to 50
to 500
Full Range = (500-50) = 450 F
27.5 50 500 522.5
Setpoint Range
5%
5%
Indicating Range
SCALING DC CURRENT/VOLTAGE INPUT RANGES
Example:
Program a 4-20mA DC signal for 0 to 100 E.U.
Input Type
Minimum/Maximum Range
4-20mA DC
-1999 . . . 9999 Enginerring Units
Program to 0
to 100
Full Range = (100-0) = 100 Engineering Units
-5 0 100 105
Setpoint Range
5%
5%
Indicating Range