5.2.5
Check voltage outputs
“
VOLTAGE OUTPUTS
” will display the screen on the right, for the
technician to select one of the 24V generic outputs for testing. During
testing the selected output will switch off for 6 seconds and switch on
again. If the switching works, the control circuit shall be functional.
Figure5-14.Check voltage
outputs
5.2.6
Check network panels
“
NETWORK PANELS
” is a function used to check panel network
communication (when activated).
When this option is selected via the Master control panel, the top line
displays the name “
MASTER PANEL
” and the next line indicates the
selected subpanel to check communication quality. Navigate between
the subpanels with up/down keys.
When this option is selected via a subpanel, the communication
quality between this subpanel and the master panel is displayed.
The following lines describe the communication quality. On normal
conditions
only “
VALID PACKETS
” counter should increase.
Figures5-15.Check network
panels