Date
27/06/2019
Document number
921100400_09_002
Page
65 of 67
65 / 67
8 Technical Characteristics
– Properties
Description
BSR-1001
Analogue Addressable
Fire Alarm Panel
1 Loop / 128 Zones
BSR-1002
Analogue Addressable
Fire Alarm Panel
2 Loops / 128 Zones
BSR-1004
Analogue Addressable
Fire Alarm Panel
4 Loops / 128 Zones
Mains power input
220-240VAC/50-60Hz
Consumption
130VA max
Battery type
2 x lead-acid batteries (Pb) 12V / 7-15Ah
Charger
Stabilized power supply 27,6V / 900mA
Loop circuits
1 loop
150 addressable points
400mA max current
2 loops
150 addressable points
per loop
400mA max current per
loop
4 loops
150 addressable points
per loop
400mA max current per
loop
Conventional
sounder / siren
circuits
4 x 24V
DC
(± 3V
DC
) / 300mA max
short / open circuit monitored
10k
Ω termination resistor
24VP Output
24V
DC
(± 3V
DC
) permanent output / 300mA max
short-circuit monitored
24VM Output
24V
DC
(± 3V
DC
) resettable output / 300mA max
short-circuit monitored
FAULT / ALARM /
AUX
Relays
potential free contacts, rated at 30V
DC
/ 5A max (resistive load)
all output relays must be protected by appropriate fuses externally dependent to
the circuit’s characteristics
Total load
2A max (including loop devices, conventional sirens, 24VM/VP outputs)
Autonomy
(on battery)
up to 72 hours (without loads at 24VM and 24VP outputs)
depending on batteries
Battery cut-off
voltage
20,5V
Battery discharge
current
2A max
Battery resistance
(ESR)
1
Ω max (higher values will lead to battery resistance fault)
Ingress protection
(case)
IP 30
Compatible cables
Cables for fire detection systems such as FIP200, MICC, PYROFIL
USB connection
Mini USB-B (2.0)