Additional information for the selected points can be displayed by
pressing the View Alarms key once. The additional information is
“
OPERATING HOURS
” and “
ALARM COUNTER
” of the specific
point.
Figure5-10.Check point 2
5.2.2
Check loop communication
“
LOOP COMMUNICATION
” option shows the screen on the right,
regarding the selected loop’s hardware data.
Navigate between the loops with up/down keys.
Figure5-11.Loop communication
5.2.3
Check conventional sirens
“
CONVENTIONAL SIRENS
” option will prompt for selecting a
conventional siren output first. By clicking Enter key, the selected
siren output will sound for 6 seconds and then stop, in order to
confirm functionality of the circuits.
Figure5-12.Check conventional
siren
5.2.4
Check relays
“
RELAYS
” will open another submenu to select a specific output relay
for testing (test circuit functionality).
“
FAULT
” option will trigger the FAULT Relay output for 6 seconds.
“
ALARM
” option will trigger the ALARM Relay output for 6 seconds.
“
AUX
” option will trigger the AUX Relay output for 6 seconds.
“
EXTRA RELAYS
” option will prompt the technician to select one of
the 8 extra relays and trigger the relay output for 6 seconds upon
selection.
Figure5-13.Check relays