DESCRIPTION

The LT NFXI-ASD Series is part of the Fire Alarm Aspiration 

Sensing Technology

®

 (FAAST) family.  FAAST is an advanced 

fire detection system for use where early warning and very early 

warning  are  a  requirement.  The  system  continuously  draws  air 

from the controlled environment through a series of sampling holes 

to monitor the environment for smoke particulate.

The NFXI-ASD is the addressable version of the FAAST LT range, 

communicating  with  the  CIE  (Fire  Panel)  via  a  proprietary  loop 

protocol.  It is available in 3 different models:

NFXI-ASD11 -

  Has single channel capability with one laser smoke 

sensor.

NFXI-ASD12 -

  Has single channel capability with two laser smoke 

sensors in a common chamber for coincidence 

detection.

NFXI-ASD22 -

  Has two channel capability with two laser smoke 

sensors in separate chambers. (one sensor for 

each channel).

This  guide  provides  information  for  mounting  and  basic  installation 

using the unit’s default factory settings.  For more advanced information 

please see the FAAST LT Advanced Setup and Control Guide.

SPECIFICATIONS
Electrical Characteristics

Voltage Range: 

18.5 - 31.5 VDC

Supply Current: 

1 Channel: 

170mA (typical); 360mA (max) @ 

24 VDC 25

o

C (excluding sounders)

 

2 Channel: 

270mA (typical); 570mA (max) @ 

24 VDC 25

o

C (excluding sounders)

Communication Loop Supply Voltage:   15 – 29 VDC (Loop current ≤ 

900mA)

Communication Loop Standby Current:  @ 24V: 900 µA max. (poll once 

every 5s)

Module Isolator Characteristics

Maximum rated switching current  

(under short circuit, Is max): 

0.9A @ ≤  29V

Maximum leakage current (IL max) 

 

with the switch open (isolated state):  15mA
Maximum series impedance with 

the switch closed (Zc max): 

190 m ohm at 15Vdc; 1A

Power Reset: 

0.5s

Configurable Input: Activation Time: 

2s (min)

Relay Contact Ratings: 

2.0 A @ 30 VDC, 0.5A @ 30 VAC

Environmental Ratings

Temperature: 

-10°C to 55°C

Relative Humidity: 

10% to 93% (non-condensing)

IP Rating: 

65

Mechanical

Exterior Dimensions: 

See Figure 1

Wiring: 

0.5 mm² to 2 mm² max

Maximum Single Pipe Length  

See Table 1A 

Maximum Number of Holes  

See Table 1A

Pipe Spec (EN54-20 Compliance):  

to EN 61386 

 

(Crush 1, Impact 1, Temp 31)

Outside Pipe Diameter: 

25mm (nom) or 27mm (nom)

Shipping Weight: 

6.5kg (inc sensors)

FIRE ALARM ASPIRATION SENSING TECHNOLOGY

®

QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT

MODELS NFXI-ASD11,  NFXI-ASD12,  NFXI-ASD22

Figure 1: Dimensions and Knock-Outs

E N G L I S H

PARTS LIST
Description Quantity

FAAST LT unit 

1

Mounting bracket 

1

3-pin Terminal block  

6

4-pin Terminal block  

1

2-pin Terminal block  

3

47 k-ohm EOL Resistor  

2

USB Cable 

1

Front Panel Labelling Pack 

1

Installation Kit CD 

1

Quick Installation Guide 

1

Important Note

Aspirating  Smoke  Detectors  supplied  and  installed  within  the 

EU  must  conform  to  the  EU  Construction  Products  Directive 

(89/106/EEC)  and  the  related  European  Product  Standard  EN 

54-20. FAAST LT has been tested and certified to ensure that it 

conforms to the necessary Standards, but strict adherence to this 

instruction guide is advised to ensure that the installation meets 

the requirements of the CPD Directive.

367

mm

135 mm

56 mm

44 mm

403

mm

356 mm

Summary of Contents for Notifier FAAST LT NFXI-ASD Series

Page 1: ...tor Characteristics Maximum rated switching current under short circuit Is max 0 9A 29V Maximum leakage current IL max with the switch open isolated state 15mA Maximum series impedance with the switch closed Zc max 190 m ohm at 15Vdc 1A Power Reset 0 5s Configurable Input Activation Time 2s min Relay Contact Ratings 2 0 A 30 VDC 0 5A 30 VAC Environmental Ratings Temperature 10 C to 55 C Relative H...

Page 2: ... labels fixed in place This allows the installer to choose the language required for the installation from the Front Panel Labelling Pack Figure 2 shows where the labels need to be placed 1 2 3 Figure 6 Fasten the mounting bracket to the wall Mounting the LT NFXI ASD to the Wall Figure 2 Placing the Front Panel Labels 2 10 3 1 4 5 6 7 8 9 2 10 3 1 4 5 6 7 8 9 IN PU T SE NS OR ASPI RATO R E L B A S...

Page 3: ...e unit Each unit has 2 pipe holes per channel so if installing a 1 channel unit holes 3 and 4 do not function Use Table 1 to locate the holes required for the installation Figure 8 Pipe Holes Table 1 Pipe Holes Used for Each FAAST LT Model Note 1 Pipe holes not used should be kept sealed Note 2 Do NOT glue pipes into the pipe holes Table 1a Maximum Number of Pipe Holes Allowed Per Channel for EN54...

Page 4: ...ANNEL 2 FILTER POWER AND ALARM CONNECTIONS CHANNEL 1 FILTER USB PORT SENSOR COVER POSITION FOR TEST MAGNET POSITION FOR TEST MAGNET Exhaust Pipe SAMPLING AREA SAMPLING AREA 5 6 EARTH BAR MOUNT EARTH BAR MOUNT EARTH BAR OPTIONAL Note 1 All wiring should comply with local requirements and regulations Note 2 Loop wiring must observe the recommendations of the panel manufacturer 3 4 ...

Page 5: ...hen smoke is detected by one of the Aspirated Smoke Detector units but not the other To avoid problems ensure that no VIEW sensors on a loop have addresses set adjacent to the address values set in an Aspirating Smoke Detector POWERING UP Using Default Settings 1 Connect a suitable 24VDC supply complying with European Standard EN 54 4 to pins 1 and 2 on terminal block T1 See Table 2 Table 3 Relays...

Page 6: ...E R F IL T E R L O W F L O W H IG H F L O W E L B A S I D M E T S Y S 2 10 3 1 4 5 6 7 8 9 MODULE 1 LEVEL 1 SMOKE FAULT FAULT POWER LEVEL 2 SMOKE MODULE 2 ALARM PREALARM IN P U T S E N S O R AS PI RA TO R E L B A S I D M E S Y TE MP ER AT UR E S O U N D E R F IL T E R L O W F L O W H IG H F L O W S T 2 10 3 1 4 5 6 7 8 9 2 10 3 1 4 5 6 7 8 9 2 Check the voltage at the connector Make sure it is wit...

Page 7: ...w when initialising POWER FAULT ON Yellow Low power alert high power fault Check the power supply voltage CHANNEL FLOW INDICATORS 1 2 ON Green The LED indicates the air flow for a channel Centre normal flow Left flow low 20 at extreme Right flow high 20 at extreme On 2 channel unit Upper row Ch1 Lower row Ch2 LOW FLOW ON Low flow fault Check filter check pipe network for blockages INPUT 1 BLINK Ex...

Page 8: ...e Mode Opening the cabinet door during normal operation will cause the unit to enter Service Mode The FILTER LEDs will blink the unit will switch off power to the fans and stops communicating with the fire panel the smoke sensors continue to communicate with the panel When the cabinet door is closed the unit restarts automatically Filters Periodic cleaning or replacement of the filters will be req...

Page 9: ...ng normal operation 1 2 3 PipeIQ LT QUICK START INSTRUCTIONS Overview of PipeIQLT The PipeIQLT software program is a convenient and powerful Windows based application that can be used to quickly and accuratelydesignpipenetworks generateconfigurationparameters for correct set up and operation and facilitate commissioning and monitoring of the performance of FAAST LT Aspiration devices PipeIQLT prov...

Page 10: ...uter in the normal way for your operating system Launching To launch the PipeIQLT application double click the PipeIQLT icon on the desktop Or click Start bottom left corner of the Windows screen and then select PipeIQLT from the programs list When the application opens it is possible to start a new project or to monitor or modify an existing project Use the File menu to select New or Open Choose ...